Manual

12
Structure6.2.
Pneumatic
connections
Locking/(shoulder) screws
as protection against pulling
off from the hub fl ange
Electrical
connections
(Cable
glands)
Sealing lug
Electronics module
(24VDC- or AS-i-
Design with service
interface, connection
terminals, DIP, Teach-
In-buttons)
Position measuring system with LED’s
Flow restriction
screw(s) of
solenoid valves
Mechanical
manual control
at solenoid
valves (red
levers)
english
13
TECHNICAL DATA7.
Operating Conditions7.1.
Ambient temperature: -10 ... +55 °C
Protection class: IP65 / IP67 according to EN 60529 or
IP69K according to IEC 40050-9
Mechanical Data7.2.
Dimensions: see data sheet
Housing material: outside: PA, PP, PPO, VA
inside: ABS, PA, PMMA
Sealing material: outside: CR, EPDM
inside: EPDM, FKM, NBR
Pneumatic Data7.3.
Control medium: Oil-free and dry air, neutral gases,
Quality classes in accordance with
DIN ISO 8573-1 (5 µm fi lter
recommended)
Dust content: max. particle size 40 µm,
(quality class 5) max. particle density 10 mg/m
3
Water content: max. pressure dew point -20 °C or
(quality class 3) min. 10 °C below the lowest
operating temperature
english
14
Oil content: max. 25 mg/m
3
(quality class 5)
Temperature range
of compressed air: -10 to +50 °C
Pressure range: 2.5 to 8 bar
Air rate of solenoid
valve: 110 I
N
/min (for de-/aeration, ventilation)
(110 I
N
/min - supplied state
200 I
N
/min - maximum typical fl ow-rate)
(Q
Nn
value according to defi nition for
pressure drop from 7 to 6 bar absolute
at +20 °C)
Connections: Intake and exhaust air connection G1/4
Working connections G1/8
Position Measuring System Data7.4.
Stroke range: 0 ... 80 mm (measuring range)
Resolution: 0.1 mm
Total fault:
± 0.5 mm - when using a target as
mentioned in the manual
Electrical Data7.5.
see chapter 9. 24 V DC - Design or 10. AS-I - Design or
11. DeviceNet- Design or 12. 120 V AC - Design .
english
15
ASSEMBLY / INSTALLATION8.
DANGER!
Risk of injury from high pressure in the equipment!
Before loosening pneumatic lines and valves, turn off
the pressure and vent the lines.
WARNING!
Risk of injury due to electrical shock!
Before reaching into the system (except for the
Teach-In procedure in a non-explosive atmosphere)
switch off the power supply and secure it to prevent
restarting!
Observe applicable accident prevention and safety
regulations for electrical equipment!
Risk of injury from improper installation!
Installation may be carried out by authorized techni-
cians only and with the appropriate tools!
Risk of injury from unintentional activation of the
system and an uncontrolled restart!
Secure system from unintentional activation.
Following assembly, ensure a controlled restart.
english
Type 8681