Manual
12
Structure6.2. 
Pneumatic 
connections
Locking/(shoulder) screws 
as protection against pulling 
off from the hub fl ange
Electrical 
connections
(Cable 
glands)
Sealing lug
Electronics module
(24VDC- or AS-i-
Design with service 
interface, connection 
terminals, DIP, Teach-
In-buttons)
Position measuring system with LED’s
Flow restriction 
screw(s) of 
solenoid valves
Mechanical 
manual control 
at solenoid 
valves (red 
levers)
english
13
TECHNICAL DATA7. 
Operating Conditions7.1. 
Ambient temperature:  -10 ... +55 °C
Protection class: IP65 / IP67 according to EN 60529 or 
            IP69K according to IEC 40050-9 
Mechanical Data7.2. 
Dimensions:    see data sheet
Housing material: outside:  PA, PP, PPO, VA
inside:   ABS, PA, PMMA
Sealing material:   outside:  CR, EPDM
inside:   EPDM, FKM, NBR
Pneumatic Data7.3. 
Control medium:   Oil-free and dry air, neutral gases, 
              Quality classes in accordance with 
              DIN ISO 8573-1 (5 µm fi lter 
           recommended)
    Dust content:    max. particle size 40 µm, 
    (quality class 5)  max. particle density 10 mg/m
3
    Water content:  max. pressure dew point -20 °C or
    (quality class 3)  min. 10 °C below the lowest
           operating temperature
english
14
    Oil content:      max. 25 mg/m
3
(quality class 5)
Temperature range 
of compressed air:    -10 to +50 °C
Pressure range:      2.5 to 8 bar
Air rate of solenoid 
valve:        110 I
N
/min (for de-/aeration, ventilation)
(110 I
N
/min - supplied state
 200 I
N
/min - maximum typical fl ow-rate)
(Q
Nn
 value according to defi nition for 
pressure drop from 7 to 6 bar absolute 
at +20 °C)
Connections:    Intake and exhaust air connection G1/4
Working connections       G1/8
Position Measuring System Data7.4. 
Stroke range:  0 ... 80 mm (measuring range)
Resolution:     0.1 mm
Total fault:  
± 0.5 mm - when using a target as 
            mentioned in the manual
Electrical Data7.5. 
see chapter 9. 24 V DC - Design  or 10. AS-I - Design  or
 11. DeviceNet- Design  or 12. 120 V AC - Design .
english
15
ASSEMBLY / INSTALLATION8. 
DANGER!
Risk of injury from high pressure in the equipment!
Before loosening pneumatic lines and valves, turn off • 
the pressure and vent the lines.
WARNING!
Risk of injury due to electrical shock!
Before reaching into the system (except for the • 
Teach-In procedure in a non-explosive atmosphere) 
switch off the power supply and secure it to prevent 
restarting!
Observe applicable accident prevention and safety • 
regulations for electrical equipment!
Risk of injury from improper installation!
Installation may be carried out by authorized techni-• 
cians only and with the appropriate tools!
Risk of injury from unintentional activation of the 
system and an uncontrolled restart!
Secure system from unintentional activation.• 
Following assembly, ensure a controlled restart.• 
english
Type 8681