Manual
16
Assembly8.1. 
For the installation of the Control Head Type 8681 to a 
process valve, you will require a process valve-specifi c hub 
fl ange as an adapter. The hub fl ange must be adapted to 
the design of the process valve.
Mount the piston rod with the target on the process 
 
valve spindle. Observe reference dimensions!
Fasten the hub fl ange on the process valve. 
During this, observe central alignment and sealing 
conditions!
Check the secure fi t of the sealing rings (in the upper  
and lower grooves).
Mount the control head on the hub fl ange (seamlessly 
 
360° rotatable). 
Secure the control head with the two locking screws  
(shoulder screws M5) in the middle grove of the hub 
fl ange (see operating instructions).
Pneumatic Installation8.2. 
Connect the required working connections 2/A1 to 2/ 
A3 (each according to model) with the corresponding 
connections on the process valve.
Connect the supply line to supply pressure connection 
 
1/P (2.5 to 8 bar).
english
17
A silencer has already been mounted on the Exhaust  
Air Connection (3/R) in the supplied state.
 1/P
Supply pressure 
connection
     3/R
Exhaust air
connection
(Silencer)
2/A3: SV 3    2/A2: SV 2    2/A1: SV 1
2/A1 ... A3 - Working connections - Solenoid valves (SV)
Sealing lugs 
at the 
housing
The fl ow restriction screws 
R and P of the solenoid valves 
(see operating instructions) are 
used for setting the air intake and 
exhaust for the working connec-
tions (for setting of the control 
speed of the process valves).
R
P
open close
english
18
Opening and Closing the 8.3. 
Housing
Opening: 
Loosen plastic self-cutting screws or seal, if housing 
 
has been secured.
Open the plastic hood by turning counterclockwise (all 
 
the way, approx. 1.5 cm). 
Closing: 
Put the plastic hood on the lower part such that the 
 
inner lugs are positioned over the fastening grooves 
and the external sealing lugs are positioned almost over 
each other. Press the hood completely over the seal of 
the lower part. 
Turn the hood by approx. 1.5 cm clockwise (meaning  
until the sealing lugs are positioned over each other).
A seal or a hood safeguard using plastic self-cutting 
screws is required in the explosion-risk area! 
Electrical Installation8.4. 
see chapter 
 9. 24 V DC - Design ,      10. AS-I - Design ,
 11. DeviceNet- Design  or  12. 120 V AC - Design .
english
19
 9. 24 V DC - DESIGN
Connection options9.1. 
left: 1 x M16 x 1,5 cable 
gland
for power supply and 
signals
left: 1 x M16 x 1,5 cable 
gland with multi-pole 
connection (M12 plug 
according to IEC 61076-
2-101, 12-pole) on a cable 
of 8 cm length
right: 1 x M16 x 1,5 cable 
gland for external initiator
right: 1 x M16 x 1,5 cable 
gland for external initiator
english
Type 8681