Manual
20
Electrical Data9.2. 
Power supply:    12 ... 28 V DC, residual ripple 10 %
Power consumption: 
(standby current):  30 mA at 24 V DC
Solenoid valves: 
    Power input per  max. 0.8 W 
    solenoid valve:  (0.9 W during activation)
    Operating mode:  Long-term operation (100 %)
Central display of the
switching states:    42 mA with a power supply of 
24 V DC per illuminated display; 
Outputs/binary 
feedback signals:  S1 out - S4 out
  Design:       Normally open contact, PNP output 
          short-circuit-proof, with self-clocking 
    short-circuit protection 
Switchable 
output current:  max. 100 mA per feedback signal
Option: Analog feedback signal:
    Signal output:   S3 out (binary feedback signal 
              S3out not available)
    Type:        Current source (4 to 20 mA)
english
21
Input / proximity switches (external initiator: S4 in):
  Power supply:  
Voltage present at control head - 10 %
Current carrying 
capacity, sensor 
power supply:  max. 90 mA;
    short-circuit protection
    Design:       DC 2- and 3-conductor, NO or NC
               (factory setting NO), PNP output
Valve control inputs (Y1 - Y3):
    Signal level - active:  U > 10 V, max. 24 V DC + 10 % 
Electrical Installation 9.3.  (24 VDC)
WARNING!
Risk of injury due to electrical shock!
Before reaching into the system (except for the • 
Teach-In procedure in a non-explosive atmosphere) 
switch off the power supply and secure it to prevent 
restarting!
Observe applicable accident prevention and safety • 
regulations for electrical equipment!
Risk of injury from improper installation!
Installation may be carried out by authorized techni-• 
cians only and with the appropriate tools!
english
22
Cable glands:
Open the housing.
 
Assemble connection cables for signals and power  
supply as well as for the external initiator.
Insert cables through the respective cable glands into 
 
the interior of the housing.
   Secure the wires to the terminal strips according to the 
pin assignments depicted in the fi gure.
Solenoid valve 
connection 
with status 
LED for SV1
Terminal strip 1
Service 
interface
DIP switches 
for color 
coding the 
LED‘s
Terminal strip 2 
(for external 
initiator)
Teach-In-
buttons T1-3
SV-connections 
with status LED
for SV2, 3
english
23
Terminal strip 1 Confi guration
24 V Power supply 24 V
GND GND
S1 OUT Output position 1
S2 OUT Output position 2
S3 OUT Output position 3 
(Option: analog signal)
S4 OUT Output external initiator
Y1 Input solenoid valve 1
Y2 Input solenoid valve 2
Y3 Input solenoid valve 3
Terminal strip 2 Confi guration
24 V Power supply 24 V for external 
initiator
S4 IN Input external initiator
GND GND external initiator
Close the housing
  .
Ensure IP protection   (dummy plugs)!
english
Type 8681