Manual

24
Cable gland with Multi-pole connection:
Internal cabling work is not required for models with multi-pole
connection. But you will require the correspondingly
assembled cable sets with the following pin assignments:
Pin Description Confi guration
1 24 V Power supply 24 V
2 GND GND
3 S1 OUT Output position 1
4 S2 OUT Output position 2
5 S3 OUT Output position 3
(Option: analog signal)
6 S4 OUT Output external initiator
7 Y1 Input solenoid valve 1
8 Y2 Input solenoid valve 2
9 Y3 Input solenoid valve 3
10-12
not used
An external initiator can be connected using the small 3-pin
terminal strip 2 (see fi gure on page 22 or manual, chapter
„Connection of an external initiator“).
english
25
Input and output signals to the higher-level control (PLC):
Pin 9 - Y3
Pin 8 - Y2
12
Pin 6 - S4 out
Pin 7 - Y1
Pin 1 - 24 V
Pin 5 - S3 out
Pin 4 - S2 out
11
Pin 3 - S1 out
Pin 2 - GND
10
(12-pole circular plug-in connector M12 x 0.75 - male,
acc. to IEC 61076-2-101 — view onto the plug pins)
english
26
10. AS-I - DESIGN
Connection options10.1.
left connection:
1 x M16 x 1,5 cable gland with Multi-pole connection
(M12 plug according to IEC 61076-2-101, 4-pole) on a
cable of 8 or 80 cm length
right connection:
1 x M16 x 1,5 cable gland for external initiator
Maximum Length of the Bus 10.2.
Line
The bus cable may be a maximum of 100 m long. When
designing the system, consider the length of the round cable
leading directly to the control head (see example calculation
in the operating instructions).
english
27
Number of Connectable 10.3.
Control Heads
In AS interface versions with extended addressing range
(A/B slave), 1 master can communicate with 62 slaves.
In AS interface versions with addressing range 31 slaves a
maximum of 31 control heads can be connected to a bus line
(the address range restriction).
10.4. Electrical Data
Power supply:
Standard: via AS-i
(29,5 ... 31,6 V DC
acc. specifi cation)
Option: externally
(19,2 V DC to 31,6 V DC)
Setting the valve’s power supply using jumpers on the
AS-interface electronics module.
Input / proximity switches (external initiator: S4 in):
Power supply: AS interface voltage present at
control head - 10 %
english
Type 8681