Manual

28
Current carrying capacity,
sensor power supply: max. 30 mA;
short-circuit protection
Design: DC 2- and 3-conductor, NO or
NC (factory setting NO), PNP
output
Inputs (from master
perspective): 3 binary feedback signals and
external initiator
Outputs (from master
perspective): 0 to 3 solenoid valves
Switching capacity: max. 0.8 W via AS interface
Pull-in current: 30 mA or 0.9 W / 200 ms
Operating mode: Long-term operation (100 %)
Central display of the switching states:
Power consumption: max. 33 mA or 1 W per illumi-
nated display (at 30.5 V AS-
interface voltage)
Power supply via AS interface bus:
Power consumption
from AS interface: max. 200 mA (incl. external
initiator with 30 mA)
Integrated short-circuit protection
english
29
External Power Supply:
Ext. power supply: 19.2 V DC to 31.6 V DC
Max. power consumption
from external power supply: 110 mA at 24 V DC
Integrated short-circuit protection
Electrical Installation (AS-i)10.5.
WARNING!
Risk of injury due to electrical shock!
Before reaching into the system (except for the
Teach-In procedure in a non-explosive atmosphere)
switch off the power supply and secure it to prevent
restarting!
Observe applicable accident prevention and safety
regulations for electrical equipment!
Risk of injury from improper installation!
Installation may be carried out by authorized techni-
cians only and with the appropriate tools!
Internal cabling work is not required for any of the AS Interface
designs with multi-pole connection. However, you will require
the correspondingly assembled cable sets with the following
pin assignments.
english
30
Pin 2
Pin 3
Pin 1
Pin 4
Likewise, the jumpers on the electronics module must be set
correspondingly (power supply via AS-i or externally) - see
page 27 .
Power supply
Pin
(via AS-i)
Confi guration
(externally)
Confi guration Color
1 AS-i+ AS-i+ brown
2 not used GND white
3 AS-i- AS-i- blue
4 not used 24 V+ black
An external initiator can be connected using the small
3-pin terminal strip 2 - see manual, chapter „Connection of
an external initiator“.
english
31
11. DEVICENET- DESIGN
Connection11.1.
left connection:
1 x M16 x 1,5 cable gland with Multi-pole connection
(M12 plug according to IEC 61076-2-101, 5-pole) on a
cable of 80 cm length
right connection:
1 x M16 x 1,5 cable gland for external initiator
DeviceNet Specifi cation11.2.
EDS fi le 8681.EDS
Icons 8681.ICO
Baud rate Factory setting: 125 kBit/s
Address Factory setting: 63
english
Type 8681