24 V DC - Design
Safety instructions10.4.
DANGER!
Danger of explosion in explosive atmosphere (only in the event of a fault as zone 2)!
Opening the hood or the housing in an explosive atmosphere is only allowed in the isolated state!•
WARNING!
Risk of injury due to electrical shock!
Before reaching into the system (except for the Teach-In procedure in a non-explosive atmosphere) switch off •
the power supply and secure it to prevent restarting!
Observe applicable accident prevention and safety regulations for electrical equipment!•
When setting the position measuring system (Teach-In), do not touch any live components!•
Risk of injury from improper installation!
Installation may be carried out by authorized technicians only and with the appropriate tools!•
Risk of injury from unintentional activation of the system and an uncontrolled restart!
Secure system from unintentional activation.•
Following installation, ensure a controlled restart.•
10.5. Electrical Installation / Start-up
10.5.1. Cable Gland with Screw-type Terminals
Procedure:
Open the housing observing the notes contained in chapter
8. Opening and Closing the Housing.
Assemble connection cables for signals and power supply as well as for the external initiator where necessary
in observance of the rules of technology.
Insert cables through the respective cable glands into the interior of the housing.
Secure the wires to the connection terminals according to the pin assignments depicted in Fig. 11.
If necessary, secure the cable with a cable tie!
Close the housing observing the notes contained in chapter
8. Opening and Closing the Housing.
NOTE!
Ensure IP protection!
To ensure IP protection, the union nuts of the cable glands must be tightened in accordance with the cable •
sizes or dummy plugs used (approx. 1.5 Nm).
If an external initiator is not used, the cable gland (wrench size 19, Ø 3 - 6 mm) must be tightly sealed with •
the dummy plug (Ø 5 - 6 mm) supplied from the factory!