Owner manual
47
DeviceNet - Design
12. DEVICENET - DESIGN
Definition12.1.
The DeviceNet is a field bus system which is based on the CAN protocol (Controller Area Network). It enables •
actuators and sensors (slaves) to be networked with higher-level controllers (master).
The control head in the DeviceNet is a slave device according to the Predefined Master/Slave Connection Set •
stipulated in the DeviceNet specification. Polled I/O, Bit Strobed I/O and Change of State (COS) are supported
as I/O connection variants.
With DeviceNet it is necessary to differentiate between cyclical or event-driven high-priority process messages •
(I/O Messages) and acyclical low-priority management messages (Explicit Messages).
The protocol process conforms to the • DeviceNet specification Release April 2010.
Electrical connection option 12.2.
Cable gland with multi-pole connection
(M12 plug according to IEC 61076-2-101, 5-pole)
Connection left: Voltage, signals
Connection right: external initiator
Connection concept DeviceNetFig. 18:
DeviceNet specification12.3.
EDS file 8681.EDS
Icons 8681.ICO
Baud rate 125 kBit/s, 250 kBit/s, 500 kBit/s (can be adjusted using DIP switches 7, 8);
factory setting: 125 kbit/s
(see chapter 12.10.2. Setting the baud rate)
Address 0 ... 63 (can be adjusted using DIP switches 1 ... 6);
factory setting: 63
(see chapter 12.10.1. Settings of the DeviceNet address)
Process data 2 static input assemblies
(Input: from the control head to the DeviceNet Master/Scanner)
1 static output assembly:
english
Control Head Type 8681