DeviceNet - Design
Online Parameterization of the Device
Devices can also be parameterized online. In doing so, you can also select whether only individual param-
eters (single) or all parameters (all) of a group are read from the device (upload) or are loaded into the device
(download).
It is also possible to transfer individual parameters or all parameters of a group cyclically in monitor mode. This
may be helpful particularly for start-up purposes.
Display of the Status LEDs in the event of a bus 12.13.
error
Bus errors are also indicated on the central three-colored status display, see chapter 16.2. Blinking
Pattern & Fault Signaling!
The device status LED
("Module") and the bus status
LED ("Network") are located on
the electronics module.
Function tests for both status LEDs after power has been switched on (connection of the network cable):
Status LED Colors of the LED Function test
"Module" green 250 ms ON (green)•
"Network" green / red 250 ms ON (green)•
250 ms ON (red)•
Then another function test is run during which the LEDs light up briefly.
When the test is complete, the status LEDs indicate the device states which are described in the following tables.
Status of the device status LED "Modules"12.13.1.
LED Device state Explanation
Off No supply Device is not supplied with voltage•
Green Device is working Normal operating state•