Owner manual
60
120 V AC - Design
13. 120 V AC - DESIGN
Electrical connection options 13.1.
Cable gland:
Connection left: Voltage, signals
Connection right: external initiator
Connection concept 120 V ACFig. 24:
Electrical Data13.2.
Central power supply: 110 to 130 V AC, 50/60 Hz
Connections: Cable gland 1 x M16 x 1.5 cable gland / SW22
for power supply and signals
clamping area 5 to 10 mm, with dummy plugs
with screwterminals for cable cross-sections of 0.5 to 1.5 mm
2
,
incl. PE connection terminal
(tightening torque of the clamping screws max. 0.5 Nm)
1 x M16 x 1.5 cable gland / SW19
for external initiator
clamping area 3 to 6 mm, with dummy plugs
with screw terminals for cable cross-sections of 0.5 to 1.5 mm²
Power consumption (standby current): 10 mA at 120 V AC
Solenoid valves:
Power consumption per solenoid valve: max. 1.4 VA (1.7 VA during activation)
Power consumption per solenoid valve: 12 mA at 120 V AC
Operating mode: Long-term operation (100 % ED)
Central display of the switching states: 13 mA with a power supply of 120 V AC per illuminated
display;
Color switching see chapter 16. LED - Color Assignments
Outputs/binary feedback signals: S1out - S3out
Design: Normally open contact, L switching,
short-circuit protection via automatically resetting fuse
switchable output current: max. 50 mA per feedback signal
Output voltage - active: ≥ (operating voltage - 2 V)
Output voltage - inactive: max. 1 V in unloaded state
english