13. PROFIBUS DP START-UP
Procedure:
Perform the automatic adjustment (X.TUNE) of the process controller.
Add the F.CONTROL auxiliary function to the main menu using the
configuration menu (ADDFUNCTION) and make settings.
Make settings in the BUS.COMM function.
Configuration of the process values.
13.1. Settings in BUS.COMM
Address 0
Enter a device address (value between 0 and 126)
BUS FAIL
Activate or deactivate approach of the safety
position
SafePos off
The actuator remains in the position which cor-
responds to the set-point value last transferred
(default setting).
SafePos on
If there is a fault in the bus communication, the
behavior of the actuator depends on the acti-
vation of the SAFEPOS auxiliary function.
SAFEPOS activated:
The actuator moves to the safety position which is specified in the
SAFEPOS auxiliary function.
SAFEPOS deactivated:
The actuator moves to the safety end position which it would
assume if the electrical and pneumatic auxiliary energy failed.
See Chapter “15. Safety end positions”.