User guide

39
DeviceNet start-up
Typ 8750
Name Description Identifier
PDO:ERR
Reset error display
If the value > 0, ERR is reset.
GSD file:
PDO: ERR
Identifier (HEX):
81, 00, 17
PDO:
MTMP
Medium temperature
Temperature in °C on 1 °C exactly
Value range 0 °C – 150 °C
GSD file:
PDO:MTMP
Identifier (HEX):
81, 40, 18
PDO:
CONact
0: Positioner
1: Process controller
GSD file:
PDO:CONact
Identifier (HEX):
81, 00, 19
Tab. 25: Process Data Output, PROFIBUS DP
14. DEVICENET START-UP
Procedure:
Perform the automatic adjustment (X.TUNE) of the process controller.
Add the F.CONTROL auxiliary function to the main menu using the
configuration menu (ADDFUNCTION) and create settings.
Make settings in the BUS.COMM function.
Configuration of the process values.
14.1. Settings in BUS.COMM
Address 0
Enter a device address (value between 0 and 63)
BAUD RATE
Selection of the baud rate
The baud rate can be changed either by pressing the operator keys
on the device or via the bus.
A change has no effect until a reset (send a reset message to
the identity object) or power up is implemented. This means if the
changed baud rate attribute is accessed before a reset or power up,
the read (changed) value does not agree with the still current baud
rate (to be changed) of the network.
Select 125 kbit/s, 250 kbit/s or 500 kbit/s
english