Start-Up
10.3. Electrical connection of the
rotating Remote Sensor to the
position controller Type 8791 or
Type 8792/8793
If necessary, shorten the cable of the Remote Sensor or extend it
to a maximum of 10 m and connect it to the designated M12 cable
gland on the position controller Type 8791 or Type 8792/8793.
Connect the 4 wires of the cable, as described in “Tab. 7” and in
the operating instructions of the position controller Type 8791 or
Type 8792/8793, to the appropriate terminals.
For potential equalization, connect the shield of the cable to the
grounding connection in the terminal compartment of the position
controller.
Wire
color
Configuration External circuit
8798 8791 or
8792/8793
brown Supply sensor +
Brown (BN)
S +
white Supply sensor –
White (WH)
S –
grey Serial interface
A cable
Grey (GY)
A
pink Serial interface
B cable
Pink (PK)
B
black Shielding
Black (BK)
Tab. 7: Wire colors and configuration; rotating Remote Sensor
11. START-UP
11.1. Safety instructions
WARNING!
Risk of injury from improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
Before start-up, ensure that the operating personnel are familiar
with and completely understand the contents of the operating
instructions.
Observe the safety instructions and intended use.
Only adequately trained personnel may operate the equipment/
the device.
No separate steps for starting up are necessary for the Remote
Sensor Type 8798.
Carry out the steps outlined for starting up in the operating
instructions of the position controller (Chapter "Start-up" in the
operating instructions of Type 8791 or Type 8792/8793).
English