Cut Sheet
BURNDY
®
Blue highlighted items are industry standard and most frequently ordered.
US: 1-800-346-4175 www.burndy.com Canada: 1-800-387-6487
TYPE YC-C
COPPER CRIMPIT™
UL Listed 90° C,
600 Volts to 35 kV ♦
Type YC-C copper CRIMPIT™ connector is a
range-taking C shape compression connector
for making tap or parallel copper connections
from #12 sol. to 4/0 strand conductor.
Catalog
Number Run Tap L
▲ Die
Index
Tools, Die Set, Catalog Number
and (‡No. of Crimps) ▲
CRIMPIT™ for 1 Str.
Copper
MD6 OUR840
Y35, Y750, Y45,
Y46* Run Tap
YC10C10 † 12 Sol.-10 Str. 12 Sol.-10 Str. 3/8" 238 W238 (1) W238 (1) U238 (1)
— —
YC8C8 8 Sol.-8 Str. 10 Sol.- 8 Str. 1/2" 162 W162 (2) W162 (2) U162** (1)
YC4C8
6 Sol.-4 Str.
8 Sol.- 8 Str.
5/8" BG or 5/8
BG (2)
W-BG** (1)
XBG (2)
XNBG (2)
U-BG (1) — —YC4C6 6 Sol.- 6 Str.
YC4C4 4 sol.- 4 Str.
YC2C4
2 Sol.-2 Str.
8 Sol.- 4 Str.
3/4" C W-C (2) — U-C (1)
1 Str. 6.8 Str., 8 Sol.
YC2C2 2 Sol.- 2 Str. — —
YC26C2
1/0 Sol.-2/0 Str.
8 Sol.- 2 Str.
11/12" E or O — —
U-E (3)
U-O (1)
1 Str. 1 or 2 Str.
YC26C26 1/0 Sol.- 2/0 Str. — —
YC28C2
3/0 Sol.-4/0 Str.
6 Sol.- 2 Str.
1-1/6" F or D3 — —
U-F (3)
U-D3** (1)
— —YC28C26 1/0 Sol.- 2/0 Str.
YC28C28 3/0.- 4/0 Str.
Features & Benets
• Range-taking conductor
◊ Lowers inventory requirements
• Compact size
◊ Easy to tape and insulate
connection
• Manufactured from high conductivity
wrought copper
◊ Provides low resistance and
excellent electrical conductivity
• Economical
◊ Provides low installed cost
† Not UL Listed.
‡ Number of Crimps.
▲ See tooling section of this catalog for complete tool
and die listings.
* Use PUADP-1 adapter when using U dies in the Y46
HYPRESS™.
** Multiple crimp die set. Makes more than one crimp per
tool compression. Figure ( ) indicates number of
compressions.
Copperweld-Copper Conductors
8A - Use CRIMPITS™ accommodating 6 str. Copper
6A - Use CRIMPITS™ accommodating 4 Str. Copper
4A - Use CRIMPITS™ accommodating 2 Str. Copper
2A - Use CRIMPITS™ accommodating 1/0 and 2/0
Copper
Bare
Copper
Compression Connections
Copper Compression — C-Tap
♦ For applications greater than 2000 Volts consult cable
manufacturer for voltage stress relief instructions.
Note: All dimensions shown are for reference only.
C-130