Alpine Installation, Operating, and Service Instructions

103448-02 - 6/13 117
Soft Lockout Codes Displayed
F. Troubleshooting problems where a Soft Lockout Code is displayed. When a soft lockout occurs, the boiler will shut
down, the display will turn red and the “Help” button will “blink”. Select the “blinking” “Help” button to determine the
cause of the soft lockout. The boiler will automatically restart once the condition that caused the lockout is corrected.
Lockout
Number
Condition Possible Cause
1
Anti Short Cycle
Minimum time between starts has not been
reached. Normal delay used to avoid excessive
cycles.
2
Boiler Safety Limit
Open
Boiler Safety Limit wired to terminals J6-1, 2 or 3
OPEN:
• Condensate Trap Float Switch contact open.
Thermal Link Switch contact open.
• Burner Door Thermostat with manual reset
contact open.
Air Pressure Switch contact open.
Auto Reset High Limit contact open.
• Loose wiring to limit device.
Auto Reset Supply high limit sensor detected temperature in excess of 200°F.
• Defective Auto Reset Supply High Limit Switch.
• Plugged Condensate Trap - also check to ensure boiler is level.
Thermal Link Switch blown due to temperature rise above 604°F. (318°C)
• Burner Door Thermostat with manual reset contact open due to temperature rise
above 500°F (260°C) - check the cause of overheating (burner door insulation,
loose mounting, etc.).
Air Pressure Switch contact open - check for blocked vent.
• See possible causes for “Hard Lockout 4”.
NOTE
Block Vent Special Note
Before a call for heat the air pressure switch is closed. When there is a call for heat
with a blocked vent the air pressure switch will open (due to excessive pressure of the
blower against a blocked ue pipe) after the blower starts. The control stops the start
sequence and stops the blower. After the blower stops the pressure switch re-closes
and the cycle continues. The displays shows the cause of trip for only the time the
pressure switch is open.
3
Boiler Safety Limit
Open
Boiler Safety Limit, or External Limit wired to
terminals J5-1 OPEN:
• Jumper for External Limit wired to terminals 11
and 12 or device connected to it open.
• Jumper for Low Water Cutoff (LWCO) Switch or
device connected to it open.
• Jumper for Low Gas Pressure Switch or
device connected to it open.
See possible causes for “Hard Lockout 4”.
Loose wiring to limit device.
External Limit defective or jumper not installed.
Low Gas Pressure Switch contact open (if installed).
LWCO switch not installed and jumper missing.
If yellow light on LWCO is on, system is low on water.
If neither yellow or green light is on, check LWCO harness.
7
Return sensor fault
Shorted or open return temperature sensor.
Shorted or mis-wired return sensor wiring.
Defective return sensor.
8
Supply sensor fault
Shorted or open supply temperature sensor.
Shorted or mis-wired supply sensor wiring.
Defective supply sensor.
9
DHW sensor fault
Shorted or open Domestic Hot Water (DHW)
temperature sensor.
Shorted or mis-wired DHW sensor wiring.
Defective DHW sensor.
10
Stack sensor fault
Shorted or open ue gas (stack) temperature
sensor.
Shorted or mis-wired stack sensor wiring.
Defective stack sensor.
11
Ignition failure
Flame failure after 5 tries to restart.
No gas pressure.
Gas pressure under minimum value shown on rating plate.
Gas line not completely purged of air.
Defective Electrode.
Loose burner ground connection.
Defective Ignition Cable.
Defective gas valve (check for 24 Vac at harness during trial for ignition before
replacing valve).
Air-fuel mixture out of adjustment - consult factory.
13
Flame rod
shorted to ground
Flame rod shorted to ground
Shorted or mis-wired ame rode wiring.
Defective ame rod.
14
DT inlet/outlet high
Temperature rise between supply and return is too
high.
Inadequate boiler water ow. Verify that circulator is operating and that circulator
and piping are sized per Section VI of this manual.
15
Return temp higher
than supply
The Control is reading a return sensor temperature
higher than the supply sensor temperature.
Condition must be present for at least 75 seconds
for this error code to appear.
Flow through boiler reversed. Verify correct piping and circulator orientation.
No boiler water ow. Verify that system is purged of air and that appropriate valves
are open.
Sensor wiring reversed.
Supply or return sensor defective.
16
Supply temp has risen
too quickly
Supply water temperature has risen too quickly.
See possible causes for “Hard Lockout 4”.
Inadequate boiler water ow.
Verify that circulator is operating and that circulator and piping are sized per
Section VI of this manual.
17
Blower speed
not proved
Normal waiting for blower speed to match purge
and light-off setpoint.
XII. Troubleshooting (continued)