Alpine Installation, Operating, and Service Instructions
103448-02 - 6/13 65
Boiler
Model
Boiler
Supply
Connection,
Inch, FPT
Boiler
Return
Connection,
Inch, FPT
Near-
Boiler
Piping
Supply
Pipe
Size,
Inch
Near-
Boiler
Piping
Return
Pipe
Size,
Inch
Max
Allowable
Flow thru
Boiler,
GPM @
20°F DT
Flow,
GPM
@ 25°F
DT
Min Req’d
Flow thru
Boiler,
GPM
@ 35°F
DT
Alliance SL
Models to
be installed
As Part of
Near-Boiler
Piping
Alliance
SL
Coil
Required
Flow Rate,
GPM
Alliance
SL Coil
Head
Loss, Ft @
Required
Flow Rate
Combined
Boiler,
Alliance SL
& Piping
Loop Head
Loss, Ft
*Recommended
Circulator
Make & Model for
Alliance SL installed
as Part of
Near-Boiler Piping
Reference
Figure
Notes
ALP080B 1 1 1 1 7.3 5.8 4.2
SL27 6 9 19.3
Taco 0014
Grundfos UPS26-99
FC (second speed)
41B
SL35 6 9 19.3
SL50 6 9.5 19.8
SL70 6 10 20.3
SL119 14 17 NA Not Recommended NA Note 1
ALP105B 1 1 1 1 9.6 7.7 5.5
SL27 6 9 19.3
Taco 0014
Grundfos UPS26-99
FC (second speed)
41B
SL35 6 9 19.3
SL50 6 9.5 19.8
SL70 6 10 20.3
SL119 14 17
NA Not Recommended
NA Note 1
ALP150B 1 1 1 1 13.8 11 7.9
SL27 6 9
41B Note 2
SL35 6 9
SL50 6 9.5
SL70 6 10
SL119 14 17 36
Taco 1400-45
Grundfos UPS 32-80/2
(max speed)
41B
NOTES:
Note 1: Required Alliance SL Coil Flow Rate exceeds Max Allowable Flow Rate thru Boiler; this Boiler/Alliance SL combination may result in boiler heat exchanger erosion and noise.
Note 2: Required Alliance SL Coil Flow Rate is below Min Required Flow Rate thru Boiler; this Model can only be installed as separate heating zone off system header - see Figure 40A for alternate
IWH piping. Indirect Water Heater Circulator must be selected by an installer based on Alliance SL required coil ow and corresponding coil head loss shown as well as total equivalent length of
such separate zone.
Note 3: Combined Head Loss shown corresponds to Min Required Flow Rate thru Boiler.
* Circulator Models shown are not equipped with internal ow check valve (IFC).
When selecting Circulators with IFC contact Circulator Manufacturer for sizing information.
Near-Boiler Piping Size shown is based on 2 to 5.5 Ft/sec velocity range to avoid potential noise and pipe erosion.
Table 20: Recommended Circulator Models for Alpine (ALP) Boilers and Alliance SL Indirect Water Heaters
Installed as Part of Near-Boiler Piping Up to 75 Ft. Equivalent Length - Domestic Hot Water Circulator
VI. Water Piping and Trim E. Multiple Boiler Installation (continued)