Install Instructions

18
ANNUAL MAINTENANCE CHECKLIST
WARNINGS
THE BOILER CONTAINS REFRACTORY
CERAMIC FIBER, a possible human carcinogen.
USE A NIOSH APPROVED RESPIRATOR when
servicing high-temperature insulation and gasket
materials. Wash exposed skin gently with soap
and water after contact Wash exposed clothing
separate from normal laundry.
LABEL ALL WIRES prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation
FAILURE TO MAINTAIN THE BOILER in proper
working condition may lead to re, explosion,
personal injury or death, and extensive property
damage.
TURN OFF ALL GAS AND ELECTRIC power
supplies to the boiler before servicing. Contact with
or release of dangerous ammable gas, electrical
voltage, moving parts, and very hot water under
pressure may cause serious personal injury,
property damage, or death.
LOCK ELECTRICAL BOXES AND GAS VALVES
CLOSED to prevent someone from inadvertently
restoring power or gas before the heating system is
safe to operate.
Refer to the information in Appendix H – Important
Product Safety Information before servicing.
Equipment you will need:
q Soft bristle brush
q Bristle ue brush
q Vacuum with brush attachment
Perform these tasks each year:
1. Clean low water cutoff probe (if applicable).
2. Inspect vent for obstruction and signs of
condensation, distortion, overheating or gas
leakage.
3. Clean vent terminal and air intake screens.
4. Inspect boiler ue passages:
(1) Remove vent pipe.
(2) Remove top panel and hood.
(3)
Remove canopy.
(4) Examine all ue passageways. Using
bristle ue brush and vacuum,
remove any soot or obstructions.
5. Remove and clean main burners:
(1) Remove jacket front panel.
(2) Disconnect pilot tubing at gas valve.
(3) Disconnect pilot lead wires at gas valve.
(4) Remove wires from ame roll-out switch.
(5) Remove burner access panel.
(6) Mark location of the pilot main burner on
the manifold if the marking on manifold
is missing or obliterated.
(7) Hold burner at throat. Lift front of burner
to clear orice (Figure AM-1). The
burner that holds the pilot can only be
removed by rst lifting the burner
adjacent to its right.
6. Perform Startup Checks and Adjustments
described earlier in this manual.
7. Check operation of airow sensing switches.
8. Check for water leaks on the boiler or water
pooling around boiler.
9. Manually operate the relief valve. If the
water is grey or black, there is excessive
oxygen in the system. Oxygen is corrosive
to boilers. Eliminate any source of oxygen.
10. Verify proper operation after servicing.
AM-1