APPENDIX D – System Piping (continued)
7. Condensation
(1) Do not over-pump. Adhere to the design
ow requirements for each zone.
(2) Adhere to the boiler’s specic
minimum return water and supply water
temperature requirements. Install a
boiler bypass, system bypass, or
primary-secondary loop when needed to
maintain water temperatures and ows
within the specied limits.
(3) Do not allow chilled water to enter the
boiler during the heating cycle, or heated
water to enter chilled water coils during
the cooling cycle.
8. Dry Fire
Install a low-water cutoff when the boiler
is installed above the level of the lowest
radiator and when required by local code.
i
The following system diagrams are intended to provide a minimum level of guidance for a
successful and trouble-free installation of the boiler in common applications. They do not substitute
for proper design, evaluation, and installation by a trained and qualified installer using the proper
tools, techniques, and design expertise. Not all options are available with every boiler.
Hot Water Boilers, Non-Condensing
Indirect Tank?
Two or more
zones of
the same
temperature?
Two or more
zones of
different
temperatures?
Two or
more
boilers?
See
Diagram
D-W1
D-W2
D-W3 Tankless Coil
D-W4
D-W5
D-W6