Install Instructions

7
or 8.4 of Natural Gas and Propane Installation Code,
CAN/CSA B149.1, or applicable provisions of local
building codes.
a. CLOSET INSTALLATIONS (conned space) in a
building of other than unusually tight construction
(see denition below), provide combustion and
ventilation air as shown in Figure 2.
b. Installations other than closet in paragraph (a) :
i. Determine volume of space (boiler room).
Rooms communicating directly with space
(through openings not furnished with doors)
are considered part of space.
Volume [ft³](m
3
) = Length [ft](m) x Width [ft]
(m) x Height [ft](m)
ii. Determine Total Input of all appliances in
space. Round result to nearest 1,000 Btu per
hour (Btuh).
iii. Determine type of space. Divide Volume by
Total Input.
• If result is greater than or equal to 50 ft³
(1.4m3) per 1,000 Btuh, space is considered
an unconnedspace.
• If result is less than 50 ft³ (1.4m3) per 1,000
Btuh, space is considered a connedspace.
iv. Determine building type. A building of
unusually tight construction has the following
characteristics:
Figure 2: Minimum Clearances
• Walls and ceiling exposed to outside
atmosphere have a continuous water vapor
retarder with a rating of 1 perm or less with
openings gasketed and sealed, and
• Weather-stripping has been added on
openable windows and doors, and
• Caulking or sealants applied in joints around
window and door frames, between sole
plates and oors, between wall-ceiling joints,
between wall panels, at plumbing and
electrical penetrations, and at other openings.
v. For boiler located in a building of other than
unusually tight construction, adequate
combustion and ventilation air is normally
provided by fresh air inltration through
cracks around windows and doors.
vi. For boiler located in building of unusually
tight construction, provide outdoor air through
two permanent openings which communicate
directly or by duct with the outdoors or spaces
(crawl or attic) freely communicating with the
outdoors. Locate one opening within 12 inches
(30.5cm) of top of space. Locate remaining
opening within 12 inches (30.5cm) of bottom
of space. Minimum dimension of air opening
is 3 inches (7.6cm). Size each opening per
following:
• Direct communication with outdoors.
Minimum free area of 1 square inch (6.5cm
2
)
per 4,000 Btu per hour input of all
equipment in space.
• Vertical ducts. Minimum free area of 1
square inch (6.5cm
2
) per 4,000 Btu per hour
input of all equipment in space. Duct
cross-sectional area shall be same as opening
free area.
• Horizontal ducts. Minimum free area of 1
square inch (6.5cm
2
) per 2,000 Btu per hour
input of all equipment in space. Duct
cross-sectional area shall be same as opening
free area.
vii. Ventilation Duct Louvers and Grilles. Equip
outside openings with louvers to prevent
entrance of rain and snow, and screens to
prevent entrance of insects and rodents.
Louvers and grilles must be xed in open
position or interlocked with equipment to open
automatically before burner operation. Screens
must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles
and screens when calculating the opening size
to provide the required free area. If free area of
louver or grille is not known, assume wood
louvers have 20-25 percent free area and metal
louvers and grilles have 60-75 percent free
area.
II. PRE-INSTALLATION AND BOILER MOUNTING (continued)
BOILER
MODEL
‘W’
202 10¾” (27.3cm)
202X 12” (30.5cm)
203 12” (30.5cm)
204 15¼” (38.7cm)
205 18½” (47.0cm)
206 21¾” (55.2cm)
207 25” (63.5cm)
208 28¼” (71.8cm)
209 31½” (80.0cm)
210 34¾” (88.3cm)