User Guide

6
SERIES 2E
Installation, Operating & Service Manual
109443-01 - 6/19
4 Clearances (continued)
Figure 4-1: Minimum Closet Clearances
Figure 4-2: Minimum Alcove Clearances
Model A B
202E 6" 14"
203E 6" 14"
204E 6" 16"
205E 6" 19"
206E 6" 22"
Model A B
207E 8" 25"
208E 8" 28"
209E 8" 31"
* Minimum radial clearance around draft hood and vent connector.
** Additional height required to maintain 6" clearance from all vent connector components. Vent damper may be
installed in vertical or horizontal section of vent connector within reach of vent damper harness.
*** Area of each opening to be 1 sq. inch for each 1000 BTU/hr input - with minimum of 100 sq. inches. Height of
opening should be half of width. 3" minimum dimension for air openings.