3. PROVIDE COMBUSTION AIR
INSUFFICIENT COMBUSTION AIR
SUPPLY may result in the production and
release of deadly carbon monoxide (CO) into the home
which can cause severe personal injury or death.
Provide combustion and ventilation air in
accordance with the section "Air for Combustion
and Ventilation," of the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, or Sections 8.2, 8.3 or 8.4
4. CONNECT VENTING
4-a
IMPROPER VENTING may result in property
damage and the release of ue gases which
contain deadly carbon monoxide (CO) into the home,
which can cause severe personal injury, death or
substantial property damage.
INSPECT EXISTING CHIMNEY before
installing boiler. Failure to clean or replace
perforated pipe or tile lining will cause severe injury
or death.
Vent installation shall be in accordance with
"Venting of Equipment," of the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, or "Venting Systems
and Air Supply for Appliances," of the Natural Gas
and Propane Installation Code, CAN/CSA B149.1,
or applicable provisions of the local building codes.
Observe all general venting guidelines provided in
Appendix B—Venting. Additionally:
1. Install any of the following for this Series 3
Category I, draft hood equipped appliance:
a. Type B or Type L gas vent. Install in
accordance with listing and manufacturer's
instructions.
b. Masonry or metal chimney. Build
and install in accordance with local
building codes; or local authority having
jurisdiction; or Standard for Chimneys,
Fireplaces, Vents, and Solid Fuel Burning
Appliances, ANSI/NFPA 211 and/or
National Building Code of Canada.
Masonry chimney must be lined with
approved clay ue lining or listed chimney
lining system.
c. Single wall metal vent. Allowed by ANSI
Z223.1/NFPA 54 under very restrictive
conditions.
d. Do not use cellular core PVC (ASTM
F891), cellular core CPVC, or Radel
®
(polyphenolsulfone).
e. Do not cover non-metallic vent pipe and
ttings with thermal insulation.
Note: Non-metallic vent cannot be used
with this boiler.
2. Attach the vent damper with three sheetmetal
screws around the perimeter of the ue collar
(Figure 4-a). The vent damper may also be
mounted anywhere between the ue outlet
and the chimney within reach of the electrical
harness.
of Natural Gas and Propane Installation Code,
CAN/CSA B149.1, or applicable provisions of the
local building codes.
Like all fuel-burning appliances, boilers need air to
operate reliably and safely.
Provide combustion air using the instructions in
Appendix A—Combustion Air.