Brochure

© 2013 U.S. Boiler Company, Inc. - Lancaster, PA
Phone: 1-888-432-8887
USBL13025 10ms
www.usboiler.net
Slenderized Radiators
Information, Specifications, & Dimensions
Center leg section furnished on 30 section and better
* Heating surface based upon the standard heat emission of
240 BTU per square foot per hour.
Add 1/2” for each bushing.
Furnished in even number section up to 48 sections.
Maximum allowable working pressure - 50 PSI, water; 15 PSI steam. Consult factory for higher pressure.
Water content - 19-4:0.08 Gal./section;25-4:0.12 Gal./section; 26-6:0.17 Gal./section
Size
No. of
Sections
Length
1-3/4” per
Sections
(inches)
Square Feet - EDR*
4-Tube 6-Tube
19” High 25” High 25” High
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
7”
10-1/2”
14”
17-1/2”
21”
24-1/2”
28”
31-1/2”
35”
38-1/2”
42”
45-1/2”
49”
52-1/2”
56”
59-1/2”
63”
66-1/2”
70”
73-1/2”
77”
80-1/2”
84”
6.4
9.6
12.8
16.0
19.2
22.4
25.6
28.8
32.0
35.2
38.4
41.6
44.8
48.0
51.2
54.4
57.6
60.8
64.0
67.2
70.4
73.6
76.8
8
12
16
20
24
28
32
36
40
44
48
52
56
60
64
68
72
76
80
84
88
92
96
12
18
24
30
36
42
48
54
60
66
72
78
84
90
96
102
108
114
120
126
132
138
144
Size H I J K L M N O
25-6
25-4
19-4
23-13/16”
23-13/16”
17-13/16”
6-15/16”
4-7/16”
4-7/16”
1-1/16”
1-1/16”
1-1/16”
1”
1”
1”
1/8”
1/8”
1/8”
21-7/16”
21-7/16”
15-7/16”
1-1/4”
1-1/4”
1-1/4”
2-1/2”
2-1/2”
2-1/2”
NPT NPT NPT
SLENDERIZED RADIATOR DIMENSIONS
Slenderized Radiators
provide heat in a low profile
package. Lower and slimmer
than most conventional
radiators, they feature a
rugged and reliable cast
iron sectional design
which easily enables the
installation of multiple units.
Obsolete sizes – All Types
Burnham Radiant Radiators
Federal - Old Style Column Radiation
Fero - 2-1/2” center
RATING - Square Feet Per Section
Height
1 Col.
2-1/2”
ctr.
2 Col.
2-1/2”
ctr.
3 Col.
2-1/2”
ctr.
4 Col.
3”
ctr.
5 Col.
3”
ctr.
14”
17”
18”
20”
22”
23”
26”
32”
38”
44”
45”
1.50
1.67
2.00
2.50
3.00
2.00
2.33
2.67
3.33
4.00
5.00
2.25
3.00
3.75
4.50
5.00
6.00
3.00
4.00
5.00
6.50
8.00
10.00
4.00
4.00
5.00
5.00
6.00
Height
RATING - Square Feet Per Section
3 Tube 4 Tube 5 Tube 6 Tube 7 Tube
14”
17”
20”
23”
26”
32”
38”
1.75
2.00
2.33
3.00
3.50
2.25
2.50
2.75
3.50
4.25
2.67
3.00
3.50
4.33
5.00
3.00
3.50
4.00
5.00
6.00
2.67
3.25
3.67
4.75
5.50
6.75
23 X 7-1/2
3.40 sq. ft. per sec.
Wall
2.25 sq. ft. per sec.
RATING - Square Feet Per Section
Height
3 Tube 4 Tube 5 Tube 6 Tube
1-1/2”
ctr.
1-3/4”
ctr.
1-1/2”
ctr.
1-3/4”
ctr.
1-1/2”
ctr.
1-3/4”
ctr.
1-1/2”
ctr.
1-3/4”
ctr.
14”
17”
19”
20”
22”
23”
25”
26”
32”
1.10
1.30
1.50
1.60
1.40
1.60
1.80
1.80
1.80
2.10
2.40
3.00
2.10
2.40
3.00
1.50
1.80
2.20
2.90
1.60
2.00
2.30
3.70
Burnham Slenderized
Recommended System Piping
ONE-PIPE STEAM
Up to 28 sq. ft. ................................................. 1 inch
Up to 62 sq. ft. ................................................. 1-1/4 inches
HOT WATER - Two-Pipe Forced Circulation
Up to 100 sq. ft. ........................... 1/2 inch
101 sq. ft. and larger .................... 3/4 inch
HOT WATER - TWO-PIPE GRAVITY SYSTEM
First floor - Up to 20 sq. ft. ............................... 1/2 inch
21 to 50 sq. ft. .............................. 3/4 inch
51 to 100 sq. ft. ............................ 1 inch
101 to 175 sq. ft. .......................... 1-1/4 inch
Second floor - Up to 30 sq. ft. .......................... 1/2 inch
31 to 70 sq. ft. .............................. 3/4 inch
71 to 120 sq. ft. ........................... 1 inch
121 to 250 sq. ft. .......................... 1 1/4 inch
Third floor - Up to 40 sq. ft. ............................. 1/2 inch
41 to 100 sq. ft. ........................... 3/4 inch
101 to 175 sq. ft. ......................... 1 inch
175 to 300 sq. ft. ......................... 1-3/4 inch
* Plug + Alternate
A B C D E
One Pipe Steam
*
supply +vent vent
*
Two Pipe Steam suppiy +supply
* *
return
Hot Water
*
supply vent
*
return
NOTES:
All sizes based on
steel pipe. Vapor
tappings, top and
bottom opposite
ends; supply 3/4 inch,
return 1/2 inch.
For tappings on
one-pipe hot water
systems see AHRI
Installation Guide.
The last connection
taken off the main
should be run to a
first floor radiator.
Radiators in which
mains terminate
should have one size
larger valves.
Heat Emission Chart
(70°F room temp)
Avg. water
temp in
radiators, °F
Heat
emission
BTU/Hr. per
sq. ft.
150
160
170
180
190
200
210
215
110
130
150
170
190
210
230
240