Specifications
14
8. PROGRAM THE CONTROLS (continued)
Please note that in operating mode to hold the 
display on the value the user can press and hold 
either the Up ñ or Down ò keys and the value 
will be continuously shown. This may be helpful in 
watching a value “live”. 
Changing the Adjustable Parameters
To adjust the Parameters such as High Limit 
Setpoint and High Limit Differential:
1.  Access the adjustment mode by pressing 
and holding the Up ñ, Down ò, and “I” 
keys simultaneously for three (3) seconds. 
This procedure is intended to discourage 
unauthorized changes or accidental changes 
to limit settings.
2.  Press the "I" key to display available 
Adjustment Mode options. Select an option.
Adjustment Mode Options
HL_
140-220°F Adjust High Limit Setting
dF_
10-30°F Adjust High Limit Differential
Or_
0-10 minutes Circulator Overrun Time
PP_
2-20 minutes Circulator Pre-purge Time
St_
140-180°F Start Temperature
Pt_
On or off Priority time
dh_
dh or tt2 DH Terminal Function
rst
Reset Lockout
f-C
F or C Select degrees F or C Mode
bac
Back to Operating Mode
3.  Press the Up ñ and Down ò keys to adjust 
the displayed item to the desired value.
4.  To return to the normal operating mode from 
the Adjustment Mode, when the "bAc” option 
is displayed, press either the Up ñ or Down 
ò key. If no keys are pressed, after ve (5) 
minutes the control will automatically return 
to the Operating Mode.
More Information about Adjustable Parameters 
1.  High Limit (HL_)
  The control is factory programmed with a 
High Limit Setpoint of 180°F. The burner 
turns "off" when the boiler temperature (bt) 
is above Operating Setpoint. The Operating 
Setpoint (SP) will equal the High Limit 
Setpoint unless an IQ Outdoor Reset IQ 
Option Card is installed. 
  The Outdoor Reset IQ Option Card reduces 
the Operating Setpoint to regulate heat 
delivery, increase home comfort and 
save energy. Refer to the Appendix I for 
additional information. The High Limit 
Setpoint is adjustable between 140° and 
220°F. 
2.  Differential (df_)
  The control is factory programmed with a 
Differential of 15°F. The Differential is the 
number of degrees the boiler temperature 
must decrease below the Operating Setpoint 
before the boiler can restart. The differential 
is adjustable between 10° through 30°F.
3.  Circulator Overrun Time (OR_)
  The control is factory programmed with 
a Circulator Overrun Time of 0 minutes. 
Circulator Overrun Time (also called 
“circulator off delay” or “circulator post 
purge”) continues circulator operation after 
a call for heat has ended, sending excess 
heat from the boiler into the system. Ensure 
system piping and zone panel settings allow 
water ow to the priority zone after the call 
for heat ends. The Circulator Overrun Time 
is adjustable between 0 through 10 minutes.
4. Circulator Pre-purge Time (PP_)
  When the boiler is warm (boiler water 
temperature higher than 140°F (adjustable 
using Start Temperature parameter)) and 
there is a thermostat call for heat, the 
system circulator is started and boiler ring 
is delayed Circulator Pre-purge minutes. If 
the temperature drops below 140°F or there 
is a DHW call for heat the boiler is started 
without delay. Additionally, the boiler is 
started without delay if the thermostat call 
for heat is initiated when the boiler water 
temperature is less than 140°F. This 
feature helps save energy by satisfying 
home heating needs with residual boiler 
heat rather than cycling the boiler. The 
Circulator Pre-purge time has a factory 
setting of 2 minutes and is eld adjustable 
between 2 and 20 minutes. When reset card 
is installed, pre-purge time may be adjusted 
down to zero (0) minutes. Refer to Table 8a.