Installation and Operation Manual

54
I.
Check pilot burner ame and main burner ames
through observation port.
1. Check pilot ame. Refer to Table 11 for appropriate
pilot detail.
2. Adjust thermostat to highest setting.
3. Check main burner ames. See Figure 47. Flame
should have clearly dened inner cones with no
yellow tipping. Orange-yellow streaks caused
by dust should not be confused with true yellow
tipping.
Yellow-tipping indicates lack of primary air.
Improper burner alignment on Main Burner Orice
will also affect primary air injection. Adjust primary
air as follows:
Figure 45: Honeywell Q3481B Pilot Flame
(24V Electronic Ignition)
Figure 44: Honeywell Q314 Pilot Flame
(24V Standing Pilot)
Figure 46: Honeywell Q179C Pilot Flame (EP)
Figure 47: Main Burner Flame
Avoid operating this boiler in an environment
where saw dust, loose insulation bers, dry wall
dust, etc. are present. If boiler is operated under
these conditions, the burner interior and ports
must be cleaned and inspected daily to insure
proper operation.
a. Loosen lock screw.
b. Close air adjustment until yellow tips appear on
ames.
c. Slowly open air adjustment until clearly dened
inner cones are visible.
d. Tighten lock screw.
4. Adjust thermostat to normal setting.