Owner's Manual

42
MODULE WATER FLOW DATA
FIGURE 3-4
1) In a primary-secondary pumping installation temperature rise thru the module has
no relation to system T. In a parallel pumping installation temperature rise thru
the module equals the temperature drop of the system.
2) In a primary-secondary pumping installation pressure drop thru the module does
not add to system circulator head. In a parallel pumping installation pressure drop
thru the module does add to system circulator head load.
3) 40°F Temperature rise thru module recommended for Primary-Secondary pumping.
Module Size Flow Rate (GPM)
Temp. Rise
Thru Module
Min. Module
Piping (NPT)
Module
Pressure Drop
805H
21 20°F 1½" 3'
14 30°F 1¼" 2'
10 40°F 1¼" 1'
806H
25 20°F 1½" 3'
17 30°F 1½" 2'
13 40°F 1¼" 1'
807HE
28 20°F 2" 3'
18 30°F 1½" 2'
14 40°F 1¼" 1'
808HE
33 20°F 2" 3'
22 30°F 1½" 3'
17 40°F 1½" 2'
809HE
37 20°F 2" 3'
25 30°F 2" 2'
19 40°F 1½" 1'
810HE
41 20°F 2" 3'
27 30°F 2" 2'
21 40°F 1½" 1'