Burnham Sage2.1 Boiler Control System (SBC2.1) – Overview (con’t)
U.S. Boiler Company – August, 2010 Page 3 of 8
Freeze Protection: If possible freezing water temperatures are detected, the
Sage2.1 will operate all pumps connected to the boiler. If water temperatures continue
to drop, the boiler will operate and heat the system slightly in order to prevent freezing
and damage to the system.
Pump Exercise: If a circulator that is connected to the Sage2.1 control does not
operate for seven (7) days, it is activated to run for twenty (20) seconds. This feature
reduces the possibility for pumps to seize and fail due to long periods of inactivity,
improving the overall reliability of the heating system.
Control Flexibility: The Sage2.1 control can respond to
multiple heating demands, and features adjustable pump
outputs, allowing for greater installation and piping flexibility.
With the touch of a button, pump outputs can be selected for
the boiler, the system, and the domestic hot water pumps. For
example, touch screen selections allow the user to set the
control for either an indirect water heater installed in a boiler
loop or in a system loop. This feature allows full pump control
for an indirect water heater piped off the system loop,
eliminating the costs of additional field-supplied relays, controls,
or wiring. And in some cases, additional savings can be
achieved by reducing the pump size for the indirect water heater.
Adaptable Firing Rate Output: The Sage2.1 can be set to respond differently to
various heat demands. This feature allows the boiler’s output to be adjusted for varying
heat loads connected to the system. For example, the boiler can be set to fire at full rate
for a DHW demand; while for a space heating demand, the Sage2.1 will limit the maximum
firing rate in systems where the domestic hot water demand requires more Btu’s than space
heating. This feature reduces boiler cycling, wear and tear on parts, and enhances heating
efficiency and comfort.
“Plug & Go” Multiple Boiler Control Sequencer: When multiple boilers are
installed, the Sequencer that is built into the Sage2.1 may be used to coordinate and
optimize the operation of up to eight (8) Sage2.1 equipped boilers. Boilers are connected
to a boiler-to-boiler
communication network
by simply "plugging-in"
standard RJ45 cables –
which can be purchased
at most electronics
stores, electric supply
distributors, & office
supply stores, or by
hard wiring between the
control panels of
multiple boilers.
Burnham Sage2.1
Control Module
.
Typical RJ45 Splitte
r