Install Instructions

108 103448-08- 9/16
Spare Part:
Sage2.2 Repair Control Kit - P/N 106191-01
Maximum Light-off Heat Rate
= 3000
Sage2.2
Repair Control Kit
P/N 106191-02
Maximum
Light-off Heat Rate
= 3000
Sage2.2
Repair Control Kit
P/N 106191-03
Maximum
Light-off Heat Rate
= 2500 rpm
Altitude 0 - 7000 Ft. 7001 - 10,000 Ft.
Boiler Type
080
-02
080
-27
105
-02
105
-27
150
-02
150
-27
210
-02
210
-27
285
-07
150
-70
210
-70
285
-70
Minimum Heat Rate 1120 1700 1250 1800 1300 2000 1370 2400 1450 2000 1800 2400
Maximum Heat Rate 4480 4480 4450 4450 5000 5000 5950 5950 5560 6200 7000 7000
Absolute
Maximum Heat Rate
5000 5000 4850 4850 5500 5500 6350 6350 6200 6200 7000 7000
Light-off Heat Rate 4000 3000 3000 2500
X. Operation F. Changing Adjustable Parameters (continued)
WARNING
Asphyxiation Hazard. Boiler type is factory set and must match the boiler model. Only change the boiler
type setting if you are installing a new or replacement Control. The boiler type setting determines minimum
and maximum blower speeds. Incorrect boiler type can cause hazardous burner conditions and improper
operation that may result in PROPERTY LOSS, PHYSICAL INJURY OR DEATH.
Table 29: Parameters Changed Using the Boiler Type Parameter Selections:
NOTE: Maximum Modulation Rates are designed for 100% nameplate rate at 0°F (-18°C) combustion air. Contact factory before
attempting to increase the Maximum Modulation Rate.
“Press”
Modulation
Setup
button to access the following parameters:
Factory
Setting
Range / Choices Parameter and Description
See Table
29
See Table 29
Boiler Type
Boiler Size Setup
To verify the boiler size selection, a qualied technician should do the following:
1. Check boilers label for actual boiler size.
2. Set “Boiler Type” to match actual boiler size.
3. Select “Conrm”.
The Boiler Type parameter changes the minimum and maximum modulation settings. This
parameter is intended to allow a user to set the parameters in a spare part Control to a particular
boiler type.