Install Instructions

110 103448-08- 9/16
X. Operation F. Changing Adjustable Parameters (continued)
“Press”
Modulation
Setup
button to access the following parameters:
Factory
Setting
Range / Choices Parameter and Description
100%
Minimum to
Maximum
Heat Rate
Central Heat Maximum Expected Heat Rate
This parameter denes the highest modulation rate the Control will go to during a central heat
call for heat. If the rated input of the installed home radiation is less than the maximum output of
the boiler, change the Central Heat Maximum Expected Heat Rate (fan speed) setting to limit the
boiler output accordingly.
80%
Minimum to
Maximum
Heat Rate
Domestic Hot Water (DHW) Maximum Expected Heat Rate
This parameter denes the highest modulation rate the Control will go to during a Domestic Hot
Water call for heat. If the rated input of the indirect water heater is less than the maximum output
of the boiler, change the DHW Maximum Expected Heat Rate (fan speed) setting to limit the boiler
output accordingly.
100%
Minimum to
Maximum
Heat Rate
Auxiliary Maximum Expected Heat Rate
This parameter denes the highest modulation rate the Control will go to during the auxiliary heat
call for heat. If the rated input of the Auxiliary Heat Zones is less than the maximum output of the
boiler, change the Auxiliary Heat Maximum Expected Heat Rate (fan speed) setting to limit the
boiler output accordingly.
40%
Minimum to
Maximum
Heat Rate
Zone 1 Expected Heat Rate (typical for zone 1 through 16)
This parameter denes the highest modulation rate the Control will go to dur-
ing the Zone 1 call for heat. If the rated input of the installed home radiation in
zone 1 is less than the maximum output of the boiler, change the Zone 1 Ex-
pected Heat Rate (fan speed) setting to limit the boiler output accordingly.
30
Minutes
0 to 60 Minutes
Zone Release Time
After the Zone Release Time minutes and a zone has not been satised (thermostat opens) the
measured heat loss will be released to increase to the Central Heat Maximum Heat Rate.
See Table
29
Minimum
- 100 to
Maximum
Minimum Heat Rate
This parameter is the lowest modulation rate the Control will go to during any call for heat.
See Table
29
See Table 29
Lightoff Heat Rate
This is the blower speed during ignition and ame stabilization periods.