Install Instructions

103448-08 - 9/16 53
3. Limestone chips will get coated by neutral salts
(product of chemical reaction between limestone
and acidic condensate) and lose neutralizing
effectiveness over time. Therefore, periodic
condensate neutralizer maintenance and limestone
chip replacement must be performed. A pH test or
acid test kits are available from HVAC/plumbing
distributors and should be used to measure
condensate acidity before/after neutralizer thus
indicating a need for service and chip replacement.
Table 11: Maximum Condensate Flow
Boiler
Model
*Maximum Condensate Flow,
GPH
ALP080B 0.9
ALP105B 1.2
ALP150B 1.7
ALP210B 2.4
ALP285B 3.2
*Assumes 100% of water in fuel condenses.
V. Condensate Disposal (continued)
Figure 19: Condensate Trap and Drain Line