Install Instructions

103448-08 - 9/16 63
VI. Water Piping and Trim E. Multiple Boiler Installation Water Piping (continued)
E. Multiple Boiler Installation Water Piping
(See Table 15 and Figures 24A, 24B, 25A and 25B)
1. Refer to this Section of this manual for:
a. Installation of Factory Supplied Piping and Trim
Components for an individual module (boiler).
b. Regarding an individual module (boiler) piping
system specic details.
c. Selection criteria for individual module (boiler)
space heating and/or DHW circulators.
2. For installations where indirect domestic hot
water heater is combined with space heating,
when sizing an indirect water heater circulator,
compare the specied ow range through an Alpine
model boiler to an indirect water heater (Alliance
SL™) model coil ow rate required to achieve water
heater rating. Refer to Table 16 and Figures 24A,
24B, 25A and 25B.
a. When Alliance SL™ model coil ow rate,
required to achieve water heater rating, falls
within the specied ow range for Alpine
boiler model, the Alliance SL™ model can be
piped as part of Alpine near-boiler piping.
Refer to Table 16 and Figures 25A and 25B.
b. When Alliance SL™ model coil ow rate,
required to achieve water heater rating,
exceeds the specied ow range for Alpine
boiler model, the Alliance SL™/Alpine boiler
combination may result in excessive noise and
boiler heat exchanger erosion, and therefore,
is not recommended. Refer to Table 16 for
details.
c. When Alliance SL™ model coil ow rate,
required to achieve water heater rating, falls
below the specied ow range for Alpine boiler
model, the Alliance SL™ model must be piped
as a separate heating zone off the system
header. The circulator must be sized based on
the Alliance SL™ model coil ow and combined
coil pressure drop and the zone piping total
equivalent length. Refer to Table 16 and Figures
24A and 24B for details.