Install Instructions

103448-02 - 6/13 43
IV. Venting E. Concentric Polypropylene Venting (continued)
Figure 26: Cutting Vent Terminal Pipe
CAUTION
Exterior wall surface must be reasonably at to
attach the Outside Wall Plate. When exterior wall
surface is not at (covered with vinyl or wood
shingle siding etc.) the siding must be removed,
and a at surface build up ash or above siding
exterior surface to secure/seal the terminal
Outside Wall Plate.
Figure 27: Completing Horizontal (Wall Terminal Installation)
Install the supplied Inside Wall Plate onto the
shortened Horizontal (Wall) Terminal interior
end and move the plate to cover interior wall
cut opening. Secure the plate with provided
fasteners, then, apply the sealant around plate
sides to seal it to interior wall (refer to Figure
27).
Lubricate the brown gasket inside boiler
concentric vent collar or the last section of
the vent pipe with small amount of water.
Ensure that inner pipe of the terminal is evenly
engaged into the gasket all around, then
push the termination male end inside boiler
concentric vent collar or the last section of
the vent pipe, until the mark (see Step v) is
no longer visible.
Re-install locking band clamp onto the joint
to secure the terminal to the collar or the last
section of the vent pipe.