Install Instructions
118
107750-01 - 9/17
Single boiler Indirect Water Heater (IWH)Piped to Primary, Optional Domestic Hot Water Priority.
Parameter Selections:
System Pump = “Central Heat,
Optional Priority”
Boiler Pump = “any demand”
DHW Pump = “Primary Loop Piped IWH”
DHW Priority Enable is optional
Explanation:
This piping arrangement permits the
system pump to run or not run when
there is a domestic hot water call for heat.
Domestic hot water priority is optional. It
is permissible for the domestic and system
pumps to run at the same time. The boiler
pump must run for every call for heat.
CAUTION: It is the installers responsibility
to select boiler piping congurations that provide
the proper ow rates and performance for the boiler
and indirect water heater.
Example Pump Parameter selections:
Explanation:
This piping arrangement only
services central heat. When
there is any demand both
boiler and system pumps turn
on.
CAUTION: It is the installers responsibility
to select boiler piping congurations that provide
the proper ow rates and performance for the
boiler.
Parameter Selection:
System pump = “Central Heat,
Optional Priority”
Boiler pump = “any demand”
DHW pump = “never”
XII. Operation F. Changing Adjustable Parameters (continued)
Single boiler with no Indirect Water Heater