Install Instructions

119
107750-01 - 9/17
Example Pump Parameter selections (continued):
XII. Operation F. Changing Adjustable Parameters (continued)
Single Boiler with Supply Piped IWH, System and DHW Wired to Master
CAUTION: It is the installers responsibility
to select boiler piping congurations that provide
the proper ow rates and performance for the boiler
and indirect water heater.
Parameter Selections:
System Pump = “Central Heat,
Optional Priority”
Boiler Pump = “any demand”
DHW Pump = “Primary Loop Piped IWH”
DHW Priority Enable is optional
Explanation:
When call for Domestic Hot Water is received
the DHW pump is turned on and the boiler
pump is turned on. This piping arrangement
permits the system pump to run or not run
when there is a domestic hot water call for
heat. Domestic hot water priority is optional.
It is permissible for the domestic and system
pumps to run at the same time. The boiler
pump must run for every call for heat.