Install Instructions
142
107750-01 - 9/17
XIV. Troubleshooting (continued)
G. Troubleshooting problems where a Hard Lockout Code is displayed. When a hard lockout occurs, the
boiler will shut down, the display will turn red and the “Help” button will “blink”. Select the “blinking” “Help” button to
determine the cause of the Hard Lockout. Once the condition that caused the lockout is corrected, the boiler will need to be
manually reset using the Reset button on the “Active Fault” display or located on the Control.
Alarm Output Contact
The Control includes an alarm output contact located on the low voltage terminal board. The alarm contact closes when the
Control goes into a manual reset Hard Lockout. The list of Hard Lockouts is shown below.
Hard Lockout Codes Displayed
Lockout Number Condition Possible Cause
4
Supply High Limit
Control supply sensor detected
temperatures in excess of 210°F.
• Heating load at time of error was far below the minimum ring
rate of the boiler.
• Defective system circulator or no ow in primary loop.
• Defective boiler circulator, no ow or insufcient ow in boiler loop.
• Control system miswired so that the boiler operation is
permitted when no zones are calling.
6
Stack High Limit
Control Flue gas (Stack) sensor
detected temperatures in excess of
214°F (101°C).
• Heat exchanger needs to be cleaned.
• Boiler over-red.
• Air-fuel mixture out of adjustment - consult factory.
12
Flame detected out of sequence
A ame signal was present when there
should be no ame.
• Defective gas valve - make sure inlet pressure is below
maximum on rating plate before replacing valve.
18
Light off rate proving failed
Blower is not running at Light-off rate
when it should or blower speed signal
not being detected by Control.
• Loose connection in 120 VAC blower wiring.
• Loose or miswired blower speed harness.
• Defective blower
19
Purge rate proving failed
Blower is not running at Purge rate
when it should or blower speed signal
not being detected by Control.
• Loose connection in 120 VAC blower wiring.
• Loose or miswired blower speed harness.
• Defective blower
20
Invalid Safety Parameters
Unacceptable Control Safety related
parameter detected.
Safety Parameter verication required. Contact factory.
21
Invalid Modulation Parameter
Unacceptable Control Modulation
related parameter detected.
Reset the control.
22
Safety data verication needed
Safety related parameter change has
been detected and a verication has
not been completed.
Safety related Control parameter has been changed and verication
has not been performed.
23
24VAC Voltage low/high
Control 24Vac control power is high
or low.
• Loose connection in 24Vac VAC power wiring.
• Loose or miswired 24Vac harness.
• Miswired wiring harness causing power supply short to ground.
• Defective transformer.
• Transformer frequency, voltage and VA do not meet
specications.
24
Fuel Valve Error
Power detected at fuel valve output
when fuel valve should be off.
• Reset the control. If problem reoccurs, replace the Control.
25
Hardware Fault
Internal control failure. • Reset the control. If problem reoccurs, replace the Control.
26
Internal Fault
Internal control failure. • Reset the control. If problem reoccurs, replace the Control.
27
Undened Fault
Undened Fault • Reset the Control. If problem reoccurs, replace the Control.
54
Air Proving Switch
Failed to Open
Air Proving Switch Failed to Open See Soft Lockout 54.










