Install Instructions
153
107750-01 - 9/17
These instructions apply only to the following altitude ranges: 2001 - 6000, 6001 - 7800, 7801 - 10,100
These instructions contain specic information to setup your boiler to ensure proper
operation.
Appendix A: Instructions for High Altitude Installations Above 2,000 ft.
Adjusting Boiler Type (must be completed rst)
Select the correct boiler size, altitude range, and fuel using
the touch screen display as follows:
1. Check boiler’s rating label for actual boiler size.
2. Conrm installation altitude
3. Power up the boiler. The display will show the
Home screen.
4. Press “Adjust” button on the Home screen.
5. Press “Adjust” button on the Adjust Mode screen.
6. Press “Login” button to access Password screen.
7. Press 5-digit display to open a keypad. Enter the
password “86” and press the return arrow to close
keypad. Press “Save” button.
8. Press “Adjust” button to enter Adjustment Mode.
9. Press “Modulation Setup” menu button.
10. Press “Adjust” button on the Boiler Type screen.
11. Use the ↓ ↑ arrow buttons to select the correct size,
altitude and fuel of your boiler. Press the (Check
with Circle) button to enter your selection.
12. Press “Enter” button until display stops blinking,
press next and repeat until “Completed” is
displayed.
13. Press X to exit.
Basic Setup Procedure for High Altitude
• After Boiler Type has been selected, proceed
to Section XI "Start-up and Checkout" to
complete boiler setup.
• See Table A2 for altitude combustion values.
• See LP Gas (Propane) Conversion Instructions
for LP Gas (propane) altitude combustion
values.
WARNING
LP Conversions - boiler setup from factory is congured for use with natural gas installed from 0 - 2,000
ft. above sea level only. For conversion to LP, use a proper conversion kit per Table 3.1. Use combustion
analyzer and follow all instructions supplied with conversion kit. If the instructions are not followed exactly,
a re, an explosion or production of carbon monoxide may result causing property damage, personal injury
or loss of life. The qualied service agency is responsible for proper installation of this boiler for use with
LP gas. The installation is not proper and complete until he operation of the converted appliance is checked
as specied in the manufacturer's instructions supplied.
These instructions include a procedure for adjusting the air-fuel mixture on this boiler. This procedure
requires a combustion analyzer to measure the CO
2
(or Oxygen) and Carbon Monoxide (CO) levels in ue
gas. Adjusting the air-fuel mixture without a proper combustion analyzer could result in unreliable boiler
operation, personal injury, or death due to carbon monoxide poisoning.
Failure to setup the boiler in accordance with these instructions could result in high amount of Carbon
Monoxide to be produced which could result in death, serious injury, and/or reduced component life.