Install Instructions

37
107750-01 - 9/17
VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
Example: A 399MBH model is to be installed as using Vent Option 34 in a masonry chimney as shown in Figure 7.23. The
following components are used:
Vent:
4" DuraVent Poly-Pro (Rigid) – 4ft
4" DuraVent Poly-Pro Flex – 30ft
Poly-Pro elbows – 2 (one at base of chimney and one above boiler)
DuraVent 4PPS-FK Terminal
Intake:
4" PVC – 6ft
4" PVC Sweep 90 – 2 (one above the boiler and one as an intake terminal)
Vent Equivalent length – First elbow is ignored. The terminal is also ignored. From Table 7.14, the equivalent length of 4"
DuraVent Poly-Pro Flex is 2.0ft. From Table 7.1 the equivalent length of the second 90 elbow is 13ft. The equivalent length
of the vent system is therefore:
4 + 13 + (30 x 2.0) = 77 ft.
Since Vent Option 34 shows a max vent length of 135ft, the planned vent length of OK.
Intake Equivalent length - First elbow and termination elbow are ignored, leaving just the straight pipe. Equivalent length of
the intake system is therefore 6ft. Since this is less than 135ft, the planned intake length is OK.
5. Use of abandoned chimney as vent chase for exible Stainless Steel Venting Option 39 - Vent Option 39 permits exible
Stainless Steel venting to be routed to the roof using an abandoned masonry type chimney. In this application, combustions
air is drawn horizontally from a wall terminal. See Figure 7.25a. When using this, observe the following requirements:
When a masonry chimney containing multiple ues is used as a chase, the exible stainless vent installation is
permitted through an adjacent UNUSED ue providing local authority having jurisdiction approves such
installation. (Figure 25b)
Masonry chimney used as a chase must be structurally sound and in good repair.
All venting is stainless steel supplied by the vent manufacturer shown in Table 7.21. The portion of this venting
within the masonry chimney is exible.
When exible stainless steel is used for combustion product venting, it must be installed at vertical or near
vertical plane. This will insure proper condensate ow back to the boiler. (Figure 7.25a)
WARNING
Asphyxiation Hazard. Flexible polypropylene vent must be installed only in an UNUSED chimney, A chimney
ue is considered UNUSED when it is not being used for any appliance venting. If chimney is a multiple ue
type where one of the multiple ues is being used for an appliance venting, the exible polypropylene vent
installation is not permitted through any of the adjacent ues.
Asphyxiation Hazard. Flexible stainless steel vent must be installed only in an UNUSED chimney ue. A
chimney ue is considered UNUSED when it is not being used for any appliance venting. If chimney is
a multiple ue type where one of the multiple ues is being used for an appliance venting, the exible
stainless vent installation is permitted through an adjacent, unused ue providing a local authority having
jurisdiction approves such installation.