Install Instructions
39
107750-01 - 9/17
VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
Option # 25 26 27 28 29 30
Option # 31 32 33 34
Illustrated in Figure 7.22 7.22 7.22 7.22 7.22 7.22 Illustrated in Figure 7.22 7.22 7.23, 7.24 7.23, 7.24
Pipe Penetration
Through Structure
Vent Roof Roof Roof Roof Roof Roof
Pipe Penetration
Through Structure
Vent Roof Roof Roof Roof
Intake Wall Wall Wall Wall Wall Wall Intake Wall Wall Wall Wall
Material
Vent
CPVC/PVC
(Note 2)
CPVC/PVC
(Note 2)
DuraVent
PolyPro
(Ridged)
DuraVent
PolyPro
(Ridged)
Selkirk
Polyue
Selkirk
Polyue
Material
Vent
Centrotherm
InnoFlue SW
Centrotherm
InnoFlue
SW
DuraVent
PolyPro
(Rigid/Flex)
DuraVent
PolyPro
(Rigid/Flex)
Intake PVC PVC PVC PVC PVC PVC Intake PVC PVC PVC PVC
Nominal Diameter
Vent 3" 4" 3" 4" 3" 4"
Nominal Diameter
Vent 3" 4" 3" 4"
Intake 3" or 4" 4" 3" or 4" 4" 3" or 4" 4" Intake 3" or 4" 4" 3" or 4" 4"
Min Equivalent Vent Length: Min Equivalent Vent Length:
Model Sizes
320 30" 30" 30" 30" 30" 30"
Model Sizes
320 30" 30" 30" 30"
399 30" 30" 30" 30" 30" 30" 399 30" 30" 30" 30"
Max Equivalent Vent Length (Note 1): Max Equivalent Vent Length (Note 1):
Model Sizes
320 60ft 135ft 60ft 135ft 60ft 135ft
Model Sizes
320 60ft 135ft 60ft 135ft
399 50ft 135ft 50ft 135ft 50ft 135ft 399 50ft 135ft 50ft 135ft
Rigid Vent Terminals
Vent
Coupling
w/Screen
Coupling
w/Screen
3PPS-12B or
3PPS-36B
w/Screen
4PPS-12B or
4PPS-36B
w/Screen
3PF-10UV or
3PF-39UV
w/Screen
4PF-10UV or
4PF-39UV
w/Screen
Rigid Vent Terminals
Vent
ISEP03 or
ISEP0339 w/
Screen
ISEP04 or
ISEP0439
w/Screen
Not Permitted
Intake
90 Elbow
w/Screen
90 Elbow
w/Screen
90 Elbow
w/Screen
90 Elbow
w/Screen
90 Elbow
w/Screen
90 Elbow
w/Screen
Intake
90 Elbow
w/Screen
90 Elbow
w/Screen
Flex Termination
& Components
(Masonry Chimney
Chase) (Note 3)
Vent
Not Permitted
Flex Termination &
Components (Masonry
Chimney Chase) (Note 3)
Vent
Not Permitted
3PPS-FK
3PPS-FLEX**
4PPS-FK
4PPS-FLEX**
Intake Intake
90 Elbow
w/Screen
90 Elbow
w/Screen
Flex Termination
& Components
(B-Vent Chimney
Chase)
Vent
Not Permitted
Flex Termination &
Components (B-Vent
Chimney Chase)
Vent
Not Permitted
3PPS-VFT
3PPS-BV*
3PPS-FLEX**
4PPS-VK
4PPS-FLEX**
Intake Intake
90 Elbow
w/Screen
90 Elbow
w/Screen
Table 7.21: Summary of Split Vent System Options (continued)
* Specify size of B vent (e.g. 3PPS-BV6 is for use with 6" B vent).
** Specify length in feet.
**** Specify Flex length and B vent diameter (e.g. IFBK022505 includes 25ft of ex and used with 5" B vent).
Note 1: Max vent lengths shown also apply to the intake. Flex vent reduces the maximum allowable vent length. See equivalent
lengths for ex vent shown in Figure 7.14 and sizing example on page 32.
Note 2: At least 30" of CPVC pipe, and at least one CPVC elbow, must be installed between the boiler's vent connection and
PVC pipe.
Note 3: If masonry chimney contains ues in addition to that being used for chase, ALL must be unused.
Note 4: See vent manufacturer's installation manual for gaskets, spacers and other required vent components.
All vertical terminals require compatible roof ashing and storm collars.