User Guide
7
User Maintenance
A. General Housekeeping (Continuous).
1. Keep boiler area clear and free of combustible
materials and obstructions to the free ow of
combustion and ventilation air to the boiler.
2. Do not store or use gasoline or other ammable
vapors, liquids or sources of hydrocarbons in the
vicinity of the boiler or any other appliance.
3. Do not store or use halogen-containing products
(bleaches, cleaners, fabric softeners, refrigerants,
chemicals, etc.) in the vicinity of the boiler.
B. Inspect Inlet Air and Vent System (Monthly). Check
the following. If corrective action is required contact
qualied service agency.
1. Inlet air terminal and vent terminal must be free of
obstruction, undamaged, with screens securely in
place.
2. Inlet air terminal, vent terminal, and wall thimble (if
used) must be weather-tight.
3. Inlet air pipe and vent pipe must be full round
shape, showing no damage from impact or excessive
temperature.
4. Inlet air pipe and vent pipe must be supported at
minimum 5 foot intervals and must not sag.
5. All inlet pipe joints must be secure and airtight.
6. All vent pipe joints must be secure and watertight.
7. Condensate drain (if used) must have minimum 6
inch trap and allow condensate to ow freely. To
clean:
a. Disconnect condensate drain from drain tting.
b. Flush condensate drain with water.
c. Securely fasten condensate drain to drain tting,
providing gas-tight and water-tight seal.
C. Inspect Pilot and Main Burner Flames (Monthly).
1. Remove jacket front panel.
2. View ames through combustion area enclosure.
See Figure 1.
3. Adjust thermostat to highest setting.
4. Check pilot ame. See Figure 4. The pilot produces
three (3) ames. The center ame should be steady,
medium hard blue enveloping
3
/8 to ½ inch of
sensing probe. If ame is yellow and lazy, follow
instructions TO TURN OFF GAS TO APPLIANCE
(see Figure 2), and contact qualied service agency.
5. Check main burner ames. See Figure 5. Flame
should have clearly dened inner cone with no
yellow tipping. Orange-yellow streaks caused
by dust should not be confused with true yellow
tipping. If yellow ames are observed, follow
instructions TO TURN OFF GAS TO APPLIANCE
(see Figure 2), and contact qualied service agency.
6. Adjust thermostat to normal setting.
D. ScheduleInspectionbyQualiedServiceAgency
(Annual or at Beginning of Heating Season). For
continued safe operation a qualied service agency
must provide a more detailed inspection of burners, heat
exchanger and vent system, and provide maintenance
as specied in Installation, Operating and Service
Instructions.
WARNING
Service on this boiler should be undertaken only by trained and skilled personnel from a qualied service
agency. Inspections should be performed at intervals specied in Installation, Operating and Service
Instructions and this manual. Maintain manuals in a legible condition.
Keep boiler area clear and free of combustible materials, gasoline and other ammable vapors and liquids.
Do not place any obstructions in boiler room that will hinder ow of combustion and ventilation air.
Figure 4: Pilot Burner