Install Instructions
10
NOTICE
The gasketed vent system components pictured below in Figure A are being phased in and each vent component 
is interchangeable with the previously supplied gasket-less venting components. The newer vent components 
are generally quicker and easier to join, as they do not require the sealant application and their clamp bands 
are attached.
In the event a gasketed vent component and a gasket-
less vent component must be interconnected, follow the 
instructions associated with Figure 8B or 8C. The two 
guiding principles of these instructions are as follows:
1) Any joining of vent components that involves 
 at least one gasket-less vent component 
 always requires the sealant application.
2) The female end of a gasket-less vent 
 component always requires a clamp band, 
 regardless of the design of the mating male 
 vent component.
Each gasket-less vent component is supplied with a clamp band and sealant.
A Vent Transition Kit, part number 6116302, is available that contains one clamp band and one 3 ounce tube 
of sealant.
Table 7: Maximum Equivalent Vent Length
Table 8: Vent System Components
V. Venting
Figure A: U.S. Boiler Company Vent
A.  General Guidelines
1.  Vent system installation must be in accordance with 
National Fuel Gas Code, ANSI Z223.1 /NFPA 54, 
Venting of Equipment, or applicable provisions of 
localbuildingcodes.Contactlocalbuildingorre
ofcialsaboutrestrictionsandinstallationinspection
in your area. This Category III venting system must 
be installed in accordance to these instructions.
2.  This boiler requires a Special Gas Vent. The product 
is designed to use supplied AL 29-4C
® 
Stainless 
Steel vent system components. The following 
manufacturer's offer similar AL 29-4C
®
 components 
and are approved for use with this product: Heat-
Fab - Saf-T-Vent (800-772-0739); Flex-L 
International - Star-34 (800-561-1980); Protech 
Systems, Inc. - FasNSeal™ (800-766-3473); and 
Z-Flex U. S., Inc. - Z-Vent (800-654-5600). The use 
of these alternate manufacturer's venting systems 
will require adapters to connect to the supplied vent 
connector and vent terminal. These adapters are not 
supplied with this boiler and should be obtained 
from the supplier of the alternate manufacturer's 
venting system. See Table 8 for complete parts list.
WARNING
Do not use this boiler with galvanized, 304 or 316 
stainless steel or any other non AL29-4C
® 
based 
vent systems.
3.  Vent length restrictions are based on equivalent 
length of vent pipe (total length of straight pipe plus 
equivalentlengthofttings).Maximumventlength
is listed in Table 7. Do not exceed maximum 
lengths. Minimum vent length is 8 feet. Table 8 lists 
equivalentlengthforttings.DonotincludeVent
Terminal in equivalent feet calculation.
IN3PVNI IN4PVNI IN5PVNI IN6PVNI
45 35 35 35
Vent System Component
Part 
Number
Equivalent 
Feet of Pipe
3" Dia. Pipe x 1 Ft 8116296U 1
3" Dia. Pipe x 3 Ft 8116298U 3
3" Dia. Pipe x 5 Ft 8116300U 5
3" Dia. Pipe x Adjustable 8116319U
Equal to 
Installed Length 
(1.1 to 1.7)
3" Dia. 90° Elbow 8116294U 5
3" Dia. 45° Elbow 8116292U 5
3" Dia. Horizontal Drain Tee 8116302U ½
3" Dia. Vertical Drain Tee 8116304U 7½
3" Single Wall Thimble 8116116 ---
3" Double Wall Thimble 103877-01 ---