Install Instructions
6
III. Steam Piping and Trim
A.  Design and install boiler and system piping to prevent 
oxygen contamination of boiler water.
  Oxygen contamination sources are system leaks 
requiringadditionofmakeupwater,ttings,and
oxygen permeable materials in distribution system. 
Eliminate oxygen contamination sources by repairing 
systemleaks,repairingttings,andusingnonpermeable
materials in distribution system.
B.  Connect system supply and return piping to boiler. 
Refer to Figure 4 for IN3PVNI or Figure 5 for 
IN4PVNI, IN5PVNI and IN6PVNI. Also consult 
Residential Hydronic Heating Installation and Design 
I=B=R Guide. Maintain minimum ½ inch clearance 
from combustible materials.
C.  Install Safety Valve in Tapping "E". See Figure 3. Use 
¾ NPT x 3" nipple and ¾ NPT elbow provided. Safety 
Valve must be installed with spindle in vertical position.
WARNING
Installation is not complete unless a safety valve 
is installed.
WARNING
Safety valve discharge piping must be piped near 
oor to eliminate potential of severe burns.  DO 
NOT pipe in any area where freezing could occur.  
DO NOT install any shut-off valves.
D.  Install Drain Valve in Tapping "D". See Figure 3. Use 2 
NPT x ¾ NPT bushing provided.
E.  Alliance SL™ Indirect Water Heater (if used). Refer 
to Alliance SL™ Installation, Operating and Service 
Instructions for additional information.
1.  Supply and Return Piping. Connect supply piping to 
Tapping "N" and return piping to Tapping "M". See 
Figure 2. Install zone circulator and strainer in 
supply piping. Install check valve to prevent gravity 
circulation of boiler water.
2.  Limit. Install temperature limit control (Honeywell 
L4006A or equal) in Tapping "P". See Figure 3. Set 
at 180°F to prevent steam production during 
non-space heating periods.
F.  Boiler, when used in connection with refrigeration 
system, must be installed so chilled medium is piped in 
parallel with boiler with appropriate valves to prevent 
chilled medium from entering boiler.
G.  Boiler piping system of hot water boiler connected to 
heating coils located in air handling units where they 
may be exposed to refrigerated air circulation must be 
equippedwithowcontrolvalvesorotherautomatic
means to prevent gravity circulation of boiler water 
during cooling cycle.
NOTICE
Before using copper for steam piping, consider the following characteristics of copper piping:
1) high coefcient of thermal expansion can induce mechanical stresses and cause expansion/ 
 contraction noises if not accounted for in the piping system design and installation,
2) high heat transfer rate (heat loss) of uninsulated copper piping must be included in the normal 
 piping and pickup factors used to size the boiler,
3) soldering or brazing pastes and uxes that end up in the system can cause poor heat transfer, 
 surging, an unsteady water line and wet steam if not thoroughly removed during the boil out 
 procedure and,
4) galvanic corrosion of the adjoining metal may occur due to dissimilar metals in certain water 
 chemistries if dielectric unions are not used.
WARNING
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.
Do not use softened water in steam boilers. Accelerated boiler corrosion will result. Tie in fresh water 
supply to the boiler upstream of a water softener.
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and can 
lead to boiler failure. U.S. Boiler Company’s Standard Warranty does not cover problems caused by 
oxygen contamination of boiler water or scale (lime) build-up caused by frequent addition of water.










