Product Overview
*Dimensions indicated are for USA only – For Canada, use dimension on next larger model.
© 2012 U.S. Boiler Company, Inc. - Lancaster, PA
Phone: 1-888-432-8887
Printed in the U.S.A.
Form No. HYDL07084-10M spm
Independence Ratings & Specications*
Model*
Input
MBH
(1)
DOE Heating
Capacity
I=B=R Rating (2)
AFUE
Approx
Shipping
Weight (Lbs.)
Minimum Chimney
Requirements
(Round) Dia.
(In.) x Ht. (Ft.) (4) (5)
Water
MBH
Steam
MBH
Steam
Sq. Ft.
IN3 62 51 44 38 158 81.9 350 4x15
IN4 105 87 76 65 271 82.0 420 5x15
IN5 140 115 100 86 358 82.0 485 6x15
IN6 175 144 125 108 450 82.1 555 6x15(5)
IN7 210 173 150 130 542 82.1 620 7x15
IN8 245 202 176 152 633 82.2 690 7x15(5)
IN9 280 231 201 174 725 82.2 760 8x15
Gross Output
MBH
Combustion
Efciency
IN10(3) 315 260 226 195 812 82.5 815 8 x15(5)
IN11(3) 349 288 250 216 900 82.5 885 9x15
IN12 385 318 276 239 996 82.5 815 9x15
Independence PV Ratings & Specications (Natural Gas, Packaged)
Boiler
Number
Input
MBH
DOE
Heating
Capacity
MBH (1)
I=B=R Net
Ratings
Maximum
Vent Length
Equivalent
Ft. (2) (3) AFUE%
Approx
Shipping
Weight
(LBS.)
Steam
MBH
Steam
Sq. Ft.
PIN3PV 62 52 39 163 45 83.2 355
PIN4PV 105 87 65 271 35 82.2 425
PIN5PV 140 116 87 363 35 82.2 490
PIN6PV 175 145 109 454 35 82.2 560
*LP available on IN3-IN9
1. Ratings shown are for installations at sea level and elevations up to 2,000 ft. For higher elevations, reduce ratings 4% for each 1,000 ft. above sea level
2. Capacities, outputs, and ratings are based on steam combustion efficiency of 82.5%.
3. For Canadian builds only: reduce input and output by 3%
4. 15 ft. height is measured from top of drafthood to top of chimney.
5. IN6, IN8, & IN10 – Canada only: Increase chimney diameter by 1”
Max Working Pressure: 15 PSI Steam
1. Capacities and ratings are based on steam combustion efficiency of 83.0%.
(84.1% for PIN3PV)
2. The approved venting system for the Independence PV is 3” AL29-4C
®
stainless steel. Do not
substitute other materials.
3. Vent pipe length is listed in equivalent feet. Any elbows or tees used can have specific values
which must be subtracted from the total length to determine maximum length of straight pipe.
Consult Installation, Operating, and Service Instructions for details.
Dimensions
Boiler
Model
A B C D E F G
IN3 14-1/2 40 33-3/4 4 40-1/4 4-3/4 7-1/4
IN4 17-3/4 40 34-3/4 5 40-1/4 4-3/4 8-7/8
IN5 21 40 35-3/4 6 40-1/4 5-1/4 10-1/2
IN6 24-1/4 40 35-3/4 6* 40-1/4 5-1/4* 12-1/8*
IN7 27-1/2 40 36-3/4 7 40-1/4 7-1/2 13-3/4
IN8 30-3/4 40 36-3/4 7* 40-1/4 7-1/2* 15-3/8*
IN9 34 40 37-3/4 8 40-1/4 7-1/2 17
IN10 37-1/4 45 38-3/4 8* 45-1/2 7-1/2 18-5/8
IN11 40-1/2 45 38-3/4 9 45-1/2 7-1/2 20-1/4
IN12 43-3/4 45 38-3/4 9 45-1/2 7-1/2 21-7/8
PIN3PV 14-1/2 45 N/A 3 N/A N/A 4
PIN4PV 17-3/4 45 N/A 3 N/A N/A 8-1/4
PIN5PV 21 45 N/A 3 N/A N/A 9-1/4
PIN6PV 24-1/4 45 N/A 3 N/A N/A 9-1/4
www.usboiler.net
Standard Equipment
(Semi Pack & K/D):
• Sectionassembly
• Insulateddeluxejacket
• Base-burnermanifoldassy.
• Flameroll-outswitch(FRS)
• Gascontrolassembly
• Canopy
• Reardrafthood
• Blockedventswitch
• Ventdamper
Packaged Boilers add:
• Pressurelimit
• 24Vtransformer
• ProbetypeLWCO
• Junctionbox
• Thermostatisolatingrelay
• Electronicignitionassembly
• 15PSIsafetyvalve
• Steamgauge
• Gaugeglass
• 3/4”drainvalve
• Wiringharness
PV Boilers add (in lieu of
chimney venting equipment):
• Induceddraftfan
• Suctionpressureswitch
• Thermostatblowerrelay
• Ventaccessorycarton:vent
connector with locking band,
vent terminal, clamp
• 3oz.tube,siliconesealant