User Guide
8
Figure 7: Typical Vent System Installation
User Maintenance
A.  General Housekeeping (Continuous)
1.  Keep boiler area clear and free of combustible 
materials and obstructions to the free ow of 
combustion and ventilation air to the boiler.
2.  Do not store or use gasoline or other ammable 
vapors or liquids in the vicinity of the boiler or any 
other appliance.
3.  Do not store or use sources of hydrocarbons in the 
vicinity of the boiler. Sources of hydrocarbons 
include bleaches, cleaners, chemicals, sprays, paint 
removers, fabric softeners, cat litter and refrigerants.
B.  Flush Low Water Cutoff (Weekly, or more 
frequently if needed). Applicable to McDonnell 
& Miller 67 oat low water cutoff only. Follow 
instructions on Blow-Down Card afxed to Jacket 
adjacent to low water cutoff.
C.  Inspect Vent System (Monthly).  See Figure 
7. Follow instructions TO TURN OFF GAS TO 
APPLIANCE (see Figure 4, 5 or 6) and contact 
a qualied service agency if any of the following 
conditions are found:
1.  Collapsed vent pipe
2.  Disconnected or loose joints
3.  Sags in horizontal runs
4.  Corrosion or other deterioration
5.  Broken or loose supports
6.  Blocked vent switch not attached to draft hood.
D.  Inspect Pilot and Main Burner Flame (Monthly).
1.  Adjust thermostat to lowest setting.
2.  Remove front removable panel. See Figure 3.
3.  Locate Pilot Observation Port. See Figure 2.
4.  Check pilot burner ame.
a.  Intermittent Ignition (EI), see Figure 9. The 
pilot burner produces three (3) ames. The 
center ame should be steady, medium hard blue 
enveloping 3/8 to ½ inch of sensing probe. If 
ames are yellow and lazy, follow instructions 
TO TURN OFF GAS TO APPLIANCE 
  (see Figure 4 for Models IN3I through IN11 or 
Figure 6 for Model IN12) and contact a qualied 
service agency.
b.  Continuous Ignition (Standing Pilot), Models 
IN10 - IN12. See Figure 8. Pilot burner 
produces three (3) ames. The center ame 
should be steady, medium hard blue enveloping 
3/8 to ½ inch of thermocouple. If ames are 
yellow and lazy, follow instructions TO TURN 
OFF GAS TO APPLIANCE (see Figure 5) and 
contact a qualied service agency.
5.  Adjust thermostat to highest setting.
6.  Check main burner ames. See Figure 10 or 11. 
Flame should have clearly dened inner cones with 
no yellow tipping. Orange-yellow streaks caused 
by dust should not be confused with true yellow 
tipping. If yellow ames are observed, follow 
instructions TO TURN OFF GAS TO APPLIANCE 
(see Figure 4, 5 or 6) and contact a qualied service 
agency.
7.  Adjust thermostat to normal setting.
WARNING
Service on this boiler should be undertaken only by trained and skilled personnel from a qualied service 
agency. Inspections should be performed at intervals specied in Installation, Operating and Service 
Instructions and this manual. Maintain manuals in a legible condition.
Keep boiler area clear and free of combustible materials, gasoline and other ammable vapors and liquids.
Do not place any obstructions in boiler room that will hinder ow of combustion and ventilation air.