VI. Gas Piping
A. Size gas Piping. Design system to provide adequate
gas supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to
boiler. Maximum allowable system pressure is ½
psig. Actual point of delivery pressure may be less;
contact gas supplier for additional information.
Minimum gas valve inlet pressure is indicated on
Rating Label, located on the vestibule panel.
2. Maximum gas demand. Table 2 lists boiler input rate.
Also consider existing and expected future gas
utilization equipment (i.e. water heater, cooking
equipment).
Table 2: Rated Input
jurisdiction specifies a gravity factor be applied. For
specific gravity greater than 0.70, apply gravity
factor from Table 5. If exact specific gravity is not
shown choose next higher value.
For materials or conditions other than those listed
above, refer to the National Fuel Gas Code, NFPA
54/ANSI Z223.1 and/or CAN/CGA B149 Installation
Codes, or size system using standard engineering
methods acceptable to authority having jurisdiction.
B. Connect boiler gas valve to gas supply system.
WARNING
Failure to properly pipe gas supply to boiler
may result in improper operation and
damage to the boiler or structure. Always
assure gas piping is absolutely leak free
and of the proper size and type for the
connected load.
An additional gas pressure regulator may be
needed. Consult gas supplier.
3. Length of piping and number of fittings. Refer to
Table 3 for maximum capacity of Schedule 40 pipe.
Table 4 lists equivalent length for standard fittings.
4. Specific gravity of gas. Gas piping systems for gas
with a specific gravity of 0.70 or less can be sized
directly from Table 3, unless authority having
1. Use methods and materials in accordance with local
plumbing codes and requirements of gas supplier. In
absence of such requirements, follow the National
Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/
CGA B149 Installation Codes.
2. Use thread (joint) compounds (pipe dope) resistant
to action of liquefied petroleum gas.
3. Install sediment trap, ground-joint union and manual
shut-off valve upstream of boiler gas valve and
outside jacket. See Figure 29.
WARNING
Failure to use proper thread compounds on
all gas connectors may result in leaks of
flammable gas.
WARNING
Gas supply to boiler and system must be
absolutely shut off prior to installing or
servicing boiler gas piping.
Figure 29: Recommended Gas Piping
Boiler
Model
Number
Rated Capacity
[cubic feet per hour]
Gas
Connection
Size
Natural LP/Propane
IN3 62 24¾ ½
IN4 105 42 ½
IN5 140 56 ½
IN6 175 70 ½
IN7 210 84 ¾
IN8 245 98 ¾
IN9 280 112 ¾
IN10 315 126 ¾*
IN11 349 13 ¾*
IN12 385 154 1
* Gas connection size is 1" on IN10 and IN11
Continuous Ignition (Standing Pilot)