K2 Installation Manual

17
107672-03 - 5/18
Figure 7.2: CPVC and PVC Elbows
Table 7.1B: Vent/ Air Intake Fitting Equivalent Length
CPVC/PVC Fitting
Equivalent
Length (ft)
PolyPro, Polyflue
or InnoFlue
Vent Fitting
Equivalent
Length (ft)
FasNSeal
Vent Fitting
Equivalent
Length (ft)
2” 90° Elbow (“Sanitary Bend”) 2.6 2” 90° Elbow 4.5
3” 90° Elbow 4.0
3” 90° Elbow (“Sanitary Bend”) 4.0 3” 90° Elbow 8.7
3” 45° Elbow 2.0
2” 90° Elbow (“Short Bend” ) 6.0 2” 45° Elbow 2.5
3” Straight Tee 18.0
3” 90° Elbow (“Short Bend”) 10.0 3” 45° Elbow 4.6
3” Boot Tee 8.0
2” 45° Elbow 1.5
3” 45° Elbow 2.0
2” Coupling 0.0
3” Coupling 0.0
VII. Venting A. Vent System Design (continued)
4. Minimum Vent and Air Intake Lengths - Observe the minimum vent lengths shown in Tables 7.5, 7.13 and 7.21.
5. Clearances to Combustibles - Maintain the following clearances from the vent system to combustible
construction:
Vent - 1/4” (also observe clearances through both combustible and non-combustible walls - see 9)
Air Intake - 0”
Concentric Portion of Concentric Terminals - 0”
6. Pitch of Horizontal Vent Piping - Pitch all horizontal vent piping so that any condensate which forms in the piping
will run towards the boiler.
Pitch CPVC/PVC vent piping 1/4” per foot.
Pitch Polypropylene vent piping 5/8” per foot.
For Category I, II, and IV boilers, have horizontal runs sloping upwards not less than 1/4” per foot (21 mm/m)
from the boiler to the vent terminal.
Les chaudières de catégories I, II et IV doivent présenter des tronçons horizontaux dont la pente montante est d’au
moins 1/4 po par pied (21 mm/m) entre la chaudière et l’évent.
NOTICE Do not exceed maximum vent/combustion air system length. Refer to Tables 7.1B, 7.5, 7.13, and
7.21 in this section for maximum vent/combustion air system length.
Use Use only vent and combustion air terminals and terminal locations shown in Tables 7.1B, 7.5, 7.13 and
7.21.