Product Overview

77
103859-12 - 8/19
MPO-IQ
Installation & Service Manual
Boiler Model
Burner
Input
(GPH)
Burner
Model
Nozzle
Air Shutter
(setting)
Air Band
(setting)
Pump
Pressure
(PSI)
Head Type
(setting)
Insertion
Depth
(Inch)
Approx.
Shipped
CO
2
(%)
Baffle
Location
(pass)
Approx. Stack
Temp. Increase
Without Baffles
°F
(2)
Approx.
Breech
Pressure
(" w.c.)
(3)
Baffles
IN
Approx.
Overfire
Pressure
(" w.c.)
(3)
Baffles OUT
Approx.
Overfire
Pressure
(" w.c.)
(3)
MPO-IQ84B 0.60 AFG
0.50 x 45W
Delavan
8
(1)
0 180 L2 2 11.5 2
nd
52 0 +0.010 +0.005
MPO-IQ115B 0.80 AFG
0.60 x 45W
Delavan
5 0 180 L2 2 11.5 2
nd
& 3
rd
84 0 +0.040 +0.020
MPO-IQ147B 1.00 AFG
0.75 x 60B
Delavan
9 0 180 L1 2 11.5 2
nd
65 0 +0.040 +0.020
MPO-IQ189B 1.30 AFG
1.00 X 60B
Delavan
7 1 180 V1 (2) 2 11.5 2
nd
39 0 +0.040 +0.030
MPO-IQ231B 1.60 AFG
1.25 x 60B
Hago
10 3 180 V1 (3) 2 11.5 2
nd
18 0 +0.050 +0.030
Notes
(1)
MPO-IQ84 at 0.60 GPH firing rate utilizes a low fire baffle.
(2)
The increased stack temperature with the baffles removed is an approximation, based on a constant supply temperature of 180°F and 11.5% CO
2
. Actual field
conditions may be different.
(3)
These values are minimum and could be as much as -.03" w.c., more without impacting performance. Pressures based on 11.5% CO
2
. Example: MPO-IQ231B
could have a breech pressure of -.03" w.c. and an overfire pressure of .020" w.c.
(4) Single stage fuel pump is standard, two-stage fuel pump is optional. Burner manufacturer has preset single stage fuel pump to settings shown in table above.
Two-stage fuel pump is factory set at 140 PSI and must be readjusted to settings shown above during burner start-up.
Table 15A: Beckett AFG Burner Specifications - Chimney Vent
Boiler Model
Burner
Input
(GPH)
Burner
Model
Nozzle
Air Gate
(setting)
Turbulator
(setting)
Pump
Pressure
(PSI)
Combustion
Head
Insertion
Depth
(Inch)
Approx.
Shipped
CO
2
(%)
Baffle
Location
(pass)
Approx. Stack
Temp. Increase
Without Baffles
°F
(2)
Approx.
Breech
Pressure
(" w.c.)
(3)
Baffles
IN
Approx.
Overfire
Pressure
(" w.c.)
(3)
Baffles OUT
Approx.
Overfire
Pressure
(" w.c.)
(3)
MPO-IQ84B 0.60 F3
.50 x 80°W
Delavan
2.5 1.0 145 SBT 6" 2.25 11.5 2
nd
52 0 +0.010 +0.005
MPO-IQ115B 0.80 F3
.65 x 70°W
Delavan
5.0 3.0 145 VSBT 2.25 11.5 2
nd
& 3
rd
84 0 +0.040 +0.020
MPO-IQ147B 1.00 F5
0.85 x 60°B
Delavan
2.7 1.0 145 LBT 10.0" 10 11.5 2
nd
65 0 +0.040 +0.020
MPO-IQ189B 1.30 F5
1.10 x 60°B
Delavan
4.5 3.0 150 SBT 6" 3.5 11.5 2
nd
39 0 +0.040 +0.030
MPO-IQ231B 1.60 F5
1.35 x 60°B
Delavan
3.5 4.0 145 VSBT 2.25 11.5 2
nd
18 0 +0.050 +0.030
Notes
(2)
The increased stack temperature with the baffles removed is an approximation, based on a constant supply temperature of 180°F and 11.5% CO
2
. Actual field
conditions may be different.
(3)
These values are minimum and could be as much as -.03" w.c., more without impacting performance. Pressures based on 11.5% CO
2
. Example: MPO-IQ231B
could have a breech pressure of -.03" w.c. and an overfire pressure of .020" w.c.
(4) Single stage fuel pump is standard, two-stage fuel pump is optional. Burner manufacturer has preset single stage fuel pump to settings shown in table above.
Two-stage fuel pump is factory set at 140 PSI and must be readjusted to settings shown above during burner start-up.
Table 15B: RIELLO 40 Burner Specifications - Chimney Vent
14 Burner Specifications