Operating instructions
20
  ITEM   FREQUENCY  ACCOMPLISHED BY  REMARKS
Atomizing Air/Steam  Annually  Service Technician  Refer to burner instructions
High and Low Gas  Monthly  Operator  Refer to burner instructions
Pressure Interlocks     
High and Low Oil  Monthly  Operator  Refer to burner instructions
Pressure Interlocks
High and Low Oil  Monthly  Operator  Refer to burner instructions
Temperature Interlocks
Fuel Valve Interlock  Annually  Service Technician  Refer to burner instruction
Switch
Purge Switch  Annually  Service Technician  Refer to burner instructions
Burner Position Interlock  Annually  Service Technician  Refer to burner instructions
Low Fire Start Interlock  Annually  Service Technician  Refer to burner instructions
Automatic Changeover  At Least Annually  Service Technician  Under supervision of gas utility
Control (dual fuel)
Safety Valves  As required  Operator  In accordance with procedure in 
        Section VI, ASME Boiler and 
        Pressure Vessel Code,   
        Recommended Rules for Care 
        and Operation of Heating   
        Boilers or Section VII for power 
      boilers.
Inspect Burner Components  Semi-annually  Service Technician  Refer to burner instructions
PERIODIC TESTING RECOMMENDED CHECK LIST