Instruction manual
30
A.   CHIMNEY VENTING 
1.  Chimney venting is an important part of a safe and efcient 
oil red appliance system.  Contact your local re and 
building ofcials on specic requirements for restrictions 
and the installation of fuel oil burning equipment. In 
addition, consult with a professional knowledgeable 
on the requirements of NFPA 31 – Standard for the 
Installation of Oil-Burning Equipment and NFPA 211 
- Standard for Chimneys, Fireplaces, Vents, and Solid 
Fuel-Burning Appliances for installations in the United 
States. Installations in Canada must be reviewed with 
a professional knowledgeable on the requirements 
of CSA B139-04 – Installation Code for Oil-burning 
Equipment. 
2.  The safe venting of oil red boilers is dependant on many 
factors. Some of these factors include:
a.  sufcient  draft  during  the  entire  heating  season  to 
allow for the safe discharge of combustion by-products 
and;
b.  suitable corrosion protection in the event of condensing 
ue gases.   Only a trained  and qualied contractor 
may install this product.
3.  The  MPO-IQ  can  be  vented  into  a  reclay  tile-lined 
masonry chimney that meets requirements outlined in 
Paragraph 4 below. It can also be vented into a chimney 
constructed from type L vent or a factory built chimney 
that complies with the type HT requirements of UL 103.  
The chimney and vent pipe shall have a sufcient draft 
at all times, to assure safe proper operation of the boiler.  
See Figure 15 for recommended installation.
WARNING
Do  not  de-rate  the  appliance.    Failure  to  re  the 
boiler at it's designed input may cause excessive 
condensation upon the interior walls of the chimney.  
In addition, the lower input may not create enough 
draft  to  adequately evacuate  the by-products  of 
combustion.
4.  Chimney Inspection – Prior to the installation of any new 
or replacement fuel burning equipment the chimney shall 
be inspected by a qualied installer. The chimney shall 
be inspected for integrity as well as for proper draft and 
condensate control. Some jurisdictions require the use 
of a liner when changing fuel types. Some jurisdictions 
require the use of a liner even when the same fuel is 
used. At a minimum, the chimney shall be examined by 
a qualied person in accordance with the requirements 
of Chapter 11 of NFPA 211, Standard for Chimneys, 
Fireplaces, Vents, and Solid Fuel-Burning Appliances.
a.  Loose Mortar – Loose mortar could be an indication 
of a prior history of condensing ue gases upon the 
inside walls of the chimney. Colder climates are more 
V. NATURAL DRAFT VENTING (All Boiler Models) 
susceptible to this condition. Under no circumstances 
shall a chimney of this condition be used until it meets 
the requirements of NFPA 211 or CSA B139-04.
b.  Unlined Chimney – Under no circumstances shall 
a chimney constructed of brick only be used. Only 
approved clay liners or listed chimney lining systems 
shall be used as specied in NFPA 31 or CSA B139-
04.
c.  Abandoned Openings – Openings through the 
chimney wall that are no longer used shall be sealed in 
accordance to NFPA 211. Often abandoned openings 
are improperly sealed and usually covered by a gypsum 
wall covering.
d.  Clean Chimney – Chimney shall be free of all loose 
debris.
5.  Draft Regulator – the draft regulator supplied with the 
boiler (or equivalent) must be used with this appliance.  
Refer to Figures 15 and 16.
B.  CHIMNEY CONNECTOR
1.  A chimney connector (vent pipe) is used to connect the 
boiler to the base of the chimney. The chimney connector 
should be kept as short as possible. The horizontal length 
of the chimney connector shall not be greater than 10 
feet.
  NOTE: Secure chimney connector to cast iron smokebox 
collar with three (3) #10 x ½" self drilling hex head TEK 
screws provided in miscellaneous parts carton. Locate 
screws around perimeter of connector as shown in Figure 
15 and approximately ½" in from edge. Use drill with 
5/16" hex bit to drive screws through connector and 
smokebox collar.
DANGER
The chimney and connector shall be inspected 
annually for signs of debris and corrosion. Loose 
mortar at the base of the chimney may be a sign 
of condensate damage to the chimney. A chimney 
professional shall be contacted immediately to 
examine the damage and recommend a solution.  
Long term operation while in this condition may 
cause a venting failure and force ue gases into the 
living space. If the chimney is to be re-lined use the 
recommendations in NFPA 31, Appendix E or CSA 
B139-04.
2.  Type B Chimney Connector - a type B chimney connector 
can be used to transmit the ue gases provided ue gas 
temperature entering the chimney connector is greater 
than 310°F.
3.  Type L Chimney Connector - a type L vent or other suitable 
material shall be used for a chimney connector if the 
temperature or exiting temperature is less than 310°F.










