Instruction manual
40
12.  Assemble the vacuum relief valve balance weight onto 
the gate. Refer to the vacuum relief valve manufacturerβs 
instructions for details.
13.  Mount the assembled vacuum relief valve gate with balance 
weight into the tee and fasten with a screw and nut in collar 
tabs. To insure proper operation, the gate must be level 
across the pivot point and plumb. Refer to the vacuum 
relief valve manufacturerβs instructions for details.
VI. DIRECT VENTING / AIR INTAKE PIPING (continued)
14.  Install remainder of air intake piping to Direct Vent 
Termination air intake collar, securing each joint with at 
least (3) sheet metal screws (installer provided) evenly 
spaced.
15.  Maintain ΒΌβ per foot slope in horizontal run to air 
intake of Direct Vent Termination.
16.  Support the air intake piping, as required, using 
perforated metal strap or other supports.
17.  Refer to Burner Manufacturer's Manual for addition 
information.