Instruction manual
54
X. OPERATING (continued)
Call for 
Heat
ZC and ZR 
Terminal 
Function
(ZC_)
Boiler 
Temp.
Boiler Status,
(B1 Output)
TT= on -- < 140 Start with no delay
TT = on -- >140 Start after 2 minute delay
ZR = on ZC_ = ZR <140 Start with no delay
ZR = on ZC_ = ZR >140  Start after 2 minute delay
ZR = on ZC_ = DH <140 Start with no delay
ZR = on ZC_ = DH >140 Start with no delay
TABLE 11: CIRCULATOR PRE-PURGE TIME EXAMPLE,
  PARAMETER PP_= 2 MINUTES
F.  CHANGING THE ADJUSTABLE PARAMETERS
  To adjust parameters such as the High Limit Setpoint and 
High Limit Differential:
1.  Using the Boiler Control display, access the adjustment 
mode by pressing and holding the Up ñ, Down ò, 
and “I” keys simultaneously for three (3) seconds. 
This procedure is intended to discourage unauthorized 
changes or accidental changes to limit settings.
2.  Press the "I" key to display available Adjustment 
Mode options. Select an option.
Adjustment Mode Options
HL_ 140-240°F Adjust High Limit Setting
HdF 10-30°F Adjust High Limit Differential
ZC_ dh, ZR or ELL ZC and ZR Terminal Function
Or_ 0-10 minutes Pump Overrun Time
PP_ 0-20 minutes Pump Pre-purge Time
St_ 140 - 180°F Start Temperature
Pt_ On or Off Priority Time
f-C F or C Select degrees F or C Mode
bac Back to Operating Mode
3.  Press the Up ñ and Down ò keys to adjust the 
displayed setpoint to the desired value.
4.  To return to the normal operating mode from the 
Adjustment Mode, when the "bAc” option is displayed, 
press either the Up ñ or Down ò key. If no keys are 
pressed, after ve (5) minutes the Boiler Control will 
automatically return to the Operating Mode.
G.  MORE INFORMATION ABOUT ADJUSTABLE 
PARAMETERS 
1.  High Limit (HL_)
  The Boiler Control is factory programmed with a 
High Limit Setpoint of 180°F. The boiler turns "off" 
when the boiler water temperature (bt) is above this 
value. The High Limit setpoint is adjustable between 
140° and 240°F. The Operating Setpoint (SP) will 
equal the High Limit Setpoint unless an Outdoor Reset 
Option Card is installed. The Outdoor Reset Option 
Card reduces the Operating Setpoint to regulate heat 
delivery, increase home comfort and save energy. 
Refer to Appendix A for additional information.
2.  Differential (HDF)
  The Boiler Control is factory programmed with a 
Differential of 15°F. The Differential is the number of 
degrees the boiler temperature must decrease below the 
Operating Setpoint before the boiler can restart. The 
differential is adjustable between 10° and 30°F.
3.  Circulator Overrun Time (OR_)
  Circulator Overrun Time (also called “circulator off 
delay” or “circulator post purge”) continues circulator 
operation after a call for heat has ended, sending 
excess heat from the boiler into the priority zone. 
Ensure system piping and zone panel settings allow 
water ow to the priority zone after the call for heat 
ends. The Circulator Overrun Time has a factor 
setting of 0 minutes and is eld adjustable between 0 
and 10 minutes.
5.  Circulator Pre-Purge Time (PP_)
  When the boiler is warm [boiler water temperature 
higher than 140°F (adjustable using Start Temperature 
parameter)] and there is a thermostat call for heat, the 
system circulator is started and boiler ring is delayed 
pre-purge minutes. If the temperature drops below 
140°F or there is a DHW Call for Heat the boiler is 
started without delay. Additionally, the boiler is started 
without delay if the thermostat call for heat is initiated 
when the boiler water temperature is less than 140°F. 
This feature helps save energy by satisfying home 
heating needs with residual boiler heat rather than 
cycling the boiler. The Circulator Pre-purge time has 
a factory setting of 2 minutes and is eld adjustable 
between 2 and 20 minutes. When reset card is installed 
pre-purge time may be adjusted down to zero (0) 
minutes. Refer to Table 11.
6. Start Temperature (St_)
  The amount of “Heat available” is calculated by 
taking the difference between measured boiler water 
temperature and the Start Temperature setting. Useful 
“Heat Available” is dependent on the type of heating 
emitter installed in the home. Heat emitters require a 
certain minimum temperature to operate effectively. 
Our default settings reect cast iron radiators. Fan 
Coils may require a start temperature setting of 180°F 
or 160°F before providing heat to the home. The Start 
Temperature has a factory setting of 140°F and is eld 
adjustable between 140°F and 180°F.