X. OPERATING (continued)
c.  External Low Limit, Parameter ZC = ELL
  The boiler control is capable of functioning as 
a warm start control when external limit control 
is installed that closes a contact when boiler 
water temperature falls below a setpoint. When 
an external limit contact closes (boiler water 
is cold) the boiler is started and the ZC and C1 
output terminals are de-energized. When the ZR 
terminal is de-energized (boiler water temperature 
is above setpoint) the call for heat is ended and 
the C1 terminal is released to operation and the 
ZC terminal is energized. An External Low Limit 
Request is detected by sensing a voltage on the ZR 
terminal. Refer to Table 14. 
TABLE 14: EXTERNAL LOW LIMIT,
 PARAMETER ZC_= ELL
Call for Heat Circulator Status
T-T
Input
ZR
Input
C1
Output
ZC
Output
off off off on
on off on  on
on on off off
off on off off