Instruction manual
57
XI. MAINTENANCE AND SERVICE INSTRUCTIONS
A.  MAINTENANCE OF LOW WATER CUT-OFF  
DEVICES (when installed)
  See Instructions provided with Low Water Cut-off Option 
Card for Installation Instructions.
WARNING
Probe type low water cut-off devices require 
annual inspection and maintenance.
1. PROBE TYPE LOW WATER CUT-OFF
  Although these devices are solid state in their operation, 
the probe is exposed to possible contamination in the 
boiler water and subject to fouling.
  Sometimes the LWCO can be found in the primary loop 
of the boiler system. Ideally, shut off valves have been 
installed between the loop containing the LWCO and 
the rest of the system, to minimize the amount of system 
draining.
  It is important to physically remove the probe from 
the LWCO tapping annually and inspect that probe for 
accumulation of scale or sediment.
  Follow these steps to inspect, clean and/or replace the 
probe:
a.  Turn off electric service to the boiler.
b.  Drain boiler water to a level below the tapping for the 
probe.
c.  Disconnect wiring connections between the low water 
cut-off control and the probe.
d.  Remove the low water cut-off control from the probe.
DANGER
Assure that the boiler is at zero pressure before 
removing the LWCO probe. Do not rely on the 
pressure gauge to indicate that the boiler is at 
zero pressure. Open the safety valve to relieve 
all internal pressure prior to proceeding. Safety 
valve discharge piping must be piped such that the 
potential for burns is eliminated.
e.  Unscrew the probe from the LWCO tapping.
f.  Inspect that portion of the probe that is exposed to the 
water for a scale or sediment buildup.
g.  Light deposits may be removed by wiping the probe 
with a damp cloth. Wiping the probe with a cloth 
soaked in vinegar will remove more tenacious lime 
deposits. The most stubborn deposits may be removed 
from the probe by using a diluted amount, 3 parts of 
water to 1 part of phosphoric acid (H
2
PO
4
).
CAUTION
Exercise caution when handling phosphoric acid 
and follow the instruction label on its container.
h.  Clean the pipe threads of the probe to remove old, 
hardened pipe dope and other foreign matter.
i.  Apply a moderate amount of good quality pipe dope 
to the pipe threads on the probe, leaving the two end 
threads bare. Do not use PTFE (Teξon) tape.
j.  Screw the probe into the LWCO tapping.
k.  Mount the low water cut-off control on the probe.
l.  Reconnect the control to probe wiring.
m. Fill the system with water.
n.  Add boiler water treatment compound as needed (refer 
to Paragraph B.).
o.  Restore electric service to the boiler.
p. Fire burner to bring the water in the boiler to a boil 
to drive off free oxygen.
q.  WARNING β BEFORE RETURNING BOILER TO  
SERVICE: Follow the low water cut-off instructions 
provided with Low Water Cut-off Option Card.
B.  BOILER AND SYSTEM CLEANING INSTRUCTIONS  
FOR TROUBLE FREE OPERATION
1.  Filling of Boiler and System β General β-In a hot water 
heating system, the boiler and entire system (other than 
the expansion tank) must be full of water for satisfactory 
operation. Water should be added to the system until the 
boiler pressure gauge registers 12 psi. To insure that the 
system is full, water should come out of all air vents when 
opened.
2.  Boiling Out of Boiler and System. The oil and grease which 
accumulate in a new hot water boiler can be washed out 
in the following manner.
a.  Ideally, shut off valves have been installed between 
the boiler return manifold and the rest of the system, 
to minimize the amount of system draining.
b.  Drain the boiler to a level below the relief valve 
tapping.
DANGER
Assure that the boiler is at zero pressure before 
removing the relief valve. Open the safety valve 
to relieve all internal pressure prior to proceeding.  
Safety valve discharge piping must be piped such 
that the potential for burns is eliminated.










